Connection procedure: frames R0...R2
WARNING!
If the drive is connected on an IT (ungrounded) system, make sure that the
EMC filter and Varistor (VAR) is disconnected. See
1. Remove the front cover as follows:
•
Loosen the retaining screw with a screwdriver (1a).
•
Lift the cover from the bottom outwards (1b).
Motor cable
2. Prepare the ends of the cable as illustrated in the figure. Two different motor
cable types are shown in the figures (2a.and 2b).
Note: The bare shield will be grounded 360°.
1a
2a
PE
Electrical installation 91
EMC filter (page
1b
85).