Assembly Of Wall Mounted Outdoor Unit - Bosch Compress 3400i AWS Installation Manual

Outdoor unit of air to water heat pump
Hide thumbs Also See for Compress 3400i AWS:
Table of Contents

Advertisement

Installation
Fig. 7
Outdoor unit at the floor bracket (view from above)
[1]
Outdoor unit
[2]
Condensation drip pan (accessory)
5.1.2

Assembly of wall mounted outdoor unit

A
1
2
Fig. 8
Wall mounted outdoor unit
[1] Wall bracket (accessory)
[2] Rubber pads
[A] Screw the wall brackets to the wall and fix the rubber pads
[B] Place the outdoor unit on the wall brackets
[C] Screw the outdoor unit to the wall brackets
Make sure that the thickness of the wall is more than 20cm and is able to
support the total load. Do not install on a light structure wall.
If the access to the outdoor unit is via a ladder, do not install the outdoor
unit more than 3m from the ground level.
10
2
1
0010036781-001
B
The condensate can either be drained away via a gravel bed or via a drain
into the building. A condensation drip pan is required for the solution
with the drain and is available as an accessory.
The condensation drip pan must be equipped with a heating cable that
runs into the pan and into the frost-free area of the drain.
An alternative solution would be to allow the condensate to seep away
naturally. This can lead to the formation of ice on the ground.
A heating cable for the drain (accessory) is required when using the
condensate collection pan.
Compress 3400i AWS – 6721825369 (2021/11)