Advertisement

5. MALFUNCTION CODE OF OUTDOOR UNIT

Table 5-1 (12/14/16 KW)
Display
Error or protection definition
E2
Communication malfunction between indoor unit and outdoor unit
E4
T3 &T4 temperature sensor malfunction
E5
Power voltage protection
E6
Fan Protection
E7
Compressor discharge temperature sensor malfunction
E9
EEPROM malfunction
E.9.
Compressor signal error
EA
A fan in the A region run for more than 5 minutes in Heat mode
Eb
2 times of E6 protection in 10 minutes
F1
The bus voltage is less than 200V for 5S
H0
Communication malfunction betweem IR341/main board
H4
3 times of L0 or L1 protection in 60 minutes
P1
Hi-pressure protection
P2
Low-pressure protection
P3
Input current protection
P4
Compressor discharge temperature protection
P5
Condenser high temperature protection
P8
Typhoon protection
PE
Indoor evaporator hi-temp protection
PL
Radiator temperature protection (Reserved)
L0
Module protection
L1
DC generatrix low voltage protection
L2
DC generatrix high voltage protection
L4
MCE malfunction
L5
Zero speed protection
L7
Phase sequence protection
L8
Speed difference >15Hz protection between the front and the back clock
L9
Speed difference >15Hz protection between the real and the setting speed
Display Function Instruction:
1. When stand by, LED displaying the amount of indoor units online which communicate with outdoor units.
2. When operation, LED displaying frequency value of compressor.
3. When defrost, LED displaying "dF".
Heat Pump Mini VRF Outdoor Unit
MALFUNCTION CODE OF OUTDOOR UNIT | 7
6 720 844 640 (2015/11)