2.4 Configuring a CS4

2.4.1
Building Technologies
CPS Fire Safety
3. When finished, stop SWE6 and then disconnect and close RCCS6.
RCCS6 tool
Note: - When the remote tunnelling technique is used, the CS6 download time
can be significantly longer than the local download time.
- During the CS6 configuration download, the communication over the LON bus
stops functioning. It then restarts automatically when the download completes.
- After the CS6 configuration change, do not forget to generate and import the
new CS6 metafile in Composer, and then download DMS8000 and NK8000
configurations.
The CS4 is an intrusion detection system with individual addressing. It consists of
the CC4 control unit, and the CT4 operating units. The ADI addressing elements
transmit the detector signals to the control unit.
The structure of the CS4 is divided into logical system levels, and planning and
parameterisation determines its allocation to software and hardware. The logical
system levels include:
Area (max. 1): Switchover level for the total alarm organisation (UNSET/SET)
l
of a building or part of a building.
Sections (max. 32): Operating level for switching ON/OFF a single or several
l
zones. Within the control unit's configuration, a section can allocate unlimited
zones.
Zones (max. 128 ): Lowest level to which the user has access. Zones must be
l
allocated to the ADI detector loops. A zone can be a single detector or a group
of detectors. Each zone has its own alarm organisation, and alarm signals are
indicated according to specific zones.
Note: There exists a special CS4 version (actually a preliminary CS440),
consisting of a CC440+CK4, that can support 256 zones.
The physical and logical configuration for a CS4 is first defined for the hardware
unit set-up, and then ported to the Composer environment using an export or "List"
file, generated by the CS4 tools.

Configuration checklist

Verify that you have satisfied the items needed in the first checklist before
proceeding to the configuration checklist that follows.
Items needed for configuration
The number of CS4s in the system.
l
The local address (111, 112, etc.) for each unit.
l
The list file generated by the CS4 tools for printed reports for each unit.
l
The connection to the DMS: Cerloop, CDI-Net, or NK8000.
l
Configuring intrusion control units
Configuring a CS4
A6V10359489_a_en
2
31
30.09.2016