Toshiba TOSVERT VF-AS3 Instruction Manual page 58

Pid control instruction manual
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Parameters of external PID4 control
Title
A370
A371
4
A372
4
A374
A375
A376
8
A377
A378
9
A379
A380
10
A381
A382
A383
A387
A389
A390
13
10. Parameter list of external PID control
Parameter name
PID control 4
PID4 set value select
PID4 feedback input select
PID4 proportional gain
PID4 integral gain
PID4 deviation upper-limit
PID4 deviation lower-limit
PID4 differential gain
PID4 set value upper-limit
PID4 set value lower-limit
PID4 start wait time
PID4 output upper-limit
PID4 output lower-limit
PID4 set value
PID4 duty control output cycle
PID4 ON-OFF control hysteresis
Adjustment range
0: Disabled
1: External Process PID control
2: External Process PID control (link with
input terminal)
3: Digital output terminal ON-OFF duty control
4 - 10: -
11: Minus external Process PID control
12: Minus external Process PID control (link
with input terminal)
0: selected by FMOd/F207
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5 - 11:-
12: A387
0: -
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
0.01 - 100.0
0.01 - 100.0
0.0 - 250.0 (%)
0.0 - 250.0 (%)
0.00 - 2.55
0.0 - 250.0 (%)
0.0 - A379 (%)
0 - 2400 (s)
0.0 - 250.0 (%)
0.0 - 250.0 (%)
A380 - A379 (%)
0 - 250 (s)
0.0 - 100.0 (%)
10-2
E6582112
Default setting
0
0
0
0.30
0.20
100.0
100.0
0.00
100.0
0.0
0
100.0
0.0
0.0
0
5.0
VF-AS3