Toshiba TOSVERT VF-AS3 Instruction Manual page 27

Pid control instruction manual
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Title
F116
F216
F217
F218
F219
The characteristics is plus when selecting minus characteristics both [F359] setting and input terminal,
2) Optional terminal input
You can input the signal into optional terminals [AI4] and [AI5] as same as analog input.
Refer to chapter 6 for detail of input characteristic setting.
3) PG feedback input
It is used in speed PID control mainly.
Set [Pt: V/f pattern] to except "10: PG feedback control" or "11: PG feedback vector control".
Example of feedback value setting
Calculate the input pulse frequency to percent base data by the following.
Set the parameters of 2 input points.
Percent base data =
Frequency command
[F237]
(60Hz)
[F235]
(0Hz)
Title
FH
F234
F235
F236
F237
F375
VF-AS3
Parameter
Terminal S3 function
II point 1 input value
II point 1 frequency
II point 2 input value
II point 2 frequency
Input pulse frequency ×100(%)
[F375: PG pulses number] × [FH: Maximum frequency]
[F234]
(0%)
Parameter name
Maximum frequency
Pulse train input point 1 input value
Pulse train input point 1 frequency
Pulse train input point 2 input value
Pulse train input point 2 frequency
PG pulses number
54: PID plus/minus switching (positive logic)
20 (%)
0 (Hz)
100 (%)
60 (Hz)
Percent base data
[F236]
(100%)
Adjustment range
30.0 - 590.0
0 - 100
0.0 - 590.0
0 - 100
0.0 - 590.0
1 - 9999
4-3
E6582112
Example of setting
Example of
setting
60(Hz)
0(%)
0(Hz)
100(%)
60(Hz)
1000
4. Setting for PID control
3
4
9