■ Parameter setting
Refer to chapter 4 and 5 for detail of parameter setting.
1) Set parameters of PG after [Pt]= "10" or "11" setting. Set [240],[F241],[F243] = "0.0(Hz)".
2
Note 1) Set [240], [F241], [F243] = "0.0(Hz)".If the setting value is different, a 0Hz command
Set value and feedback value are below. (not select)
Set value
Feedback value
2) Set the following parameters to suit the motor if necessary.
9
3) Set the following parameters to suit the system.
Limit the level of PID output.
Output of agreement signal
between set value and
feedback value.
2. PID control selection
Title
Parameter name
Pt
V/f Pattern
F375
PG pulses number
F376
PG select
F377
PG option disconnection detection
F379
PG option voltage
F240
Start frequency
F241
Run frequency
F243
End frequency
cannot be output, resulting in incorrect operation of the easy positioning PID control.
Item
0 (pulse)
Current position (Pulse number from the set value)
Title
Parameter name
FH
Maximum frequency
UL
Upper limit frequency
LL
Lower limit frequency
Item
Title
F370
F371
F381
Output terminal function "118/119: Stop positioning
completion"
Function
Parameter name
PID1 output upper-limit
PID1 output lower-limit
Simple positioning completion range
2-6
E6582112
VF-AS3