3.2.8 Routing Cables

3.2.8.1 Top Cable Routing

UPS5000-E-120K-F120 and UPS5000-E-200K-F200
The UPS5000-E-120K-F120 and UPS5000-E-200K-F200 use the same top cable routing
mode. To route cables from the top of the UPS5000-E-320K-F320, configure a top entry
cabinet.
To route cables from the top of the UPS5000-E-120K-F120 or UPS5000-E-200K-F200,
perform the following steps:
Step 1 Open the front door, and remove the cover from the power distribution subrack, as shown in
Figure
Figure 3-22 Removing the cover
Issue 10 (2015-09-15)
Perform the following steps to route cables from the top.
The basic rule is to route cables from inside out and from the bottom up.
After routing cables, use fireproof mud to fill in the gap between the cables and the
cabinet.
3-22.