Huawei UPS5000-E-12 User Manual page 49

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual
Connector
connector
Bypass input
connector
Battery input
connector
Output
connector
Grounding
connector
Table 3-6
UPS5000-E.
Table 3-6 Upstream input circuit breaker configurations
Upstream
Input
Circuit
Breaker
Upstream
mains input
switch
Upstream
bypass
input
switch
Table 3-7 Upstream input circuit breakers
Model
UPS5000-E-1
20K-F120
Issue 10 (2015-09-15)
Connection
Mode
terminals
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
lists the recommended upstream input circuit breaker configurations for the
UPS5000-E-120K-F120
40
80
kVA
kVA
Three-
Three-
pole,
pole,
100 A
160 A
Three-
Three-
pole,
pole,
100 A
160 A
UPS
Capacity
40 kVA
80 kVA
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Bolt Type
M12
M12
M12
M12
UPS5000-E-200
K-F200
120
160
200
kVA
kVA
kVA
Three-
Three-
Three-
pole,
pole,
pole,
250 A
400 A
400 A
Three-
Three-
Three-
pole,
pole,
pole,
250 A
400 A
400 A
Component
Mains input circuit
breaker
Bypass input circuit
breaker
Mains input circuit
breaker
Bypass input circuit
breaker
3 Installation
Bolt Hole
Torque
Diameter
46 N•m
13.5 mm
46 N•m
13.5 mm
46 N•m
13.5 mm
46 N•m
13.5 mm
UPS5000-E-320K-F320/
UPS5000-E-320K-F320T
240
280
kVA
kVA
Three-
Three-
pole,
pole,
500 A
500 A
Three-
Three-
pole,
pole,
500 A
500 A
Specification
Manufactur
s
er
T1N160 TMD
ABB
R100 FFC 3P
(recommende
d when the
T1N160 TMD
short-circuit
R100 FFC 3P
current where
the switch is
T1N160 TMD
located is
R160 FFC 3P
less than 36
kVA.)
T1N160 TMD
R160 FFC 3P
320
kVA
Three-
pole,
630 A
Three-
pole,
630 A
40

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-20Ups5000-e-3200k-f1200k-f200K-f320K-f320t

Table of Contents