UPS5000-E-(40 kVA-320 kVA)
User Manual
Step 2 After the inverter shuts down, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is abnormal, the UPS supplies no power, and the loads shut down, as shown in
Figure
Figure 5-17 Bypass mode
After you shut down the inverter, the Bypass mode alarm is displayed on the LCD.
Step 3 After the inverter shuts down, open the UPS output switch on the output PDC, or turn off the
external output distribution switch.
Issue 10 (2015-09-15)
c.
On the homepage, choose Monitoring > Control, and click Inverter Off. In the
displayed dialog box, click OK to shut down the inverter, as shown in
Figure 5-16 Shutting down the inverter
5-17.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Operations
Figure
5-16.
161