• If the Pr.1076 setting is too large (the width is too wide), the response level of speed control drops, and the system may
become unstable.
• After setting Pr.1074 = "9999", set the crane rope length in the Pr.1077 Rope length, the trolley weight in the Pr.1078
Trolley weight, and the weight of an object in the Pr.1079 Load weight. Then, anti-sway control is performed using a
swinging frequency estimated by the inverter.
 Delay time for brake operation of anti-sway control (Pr.1072)
• Set the time from when the output frequency becomes the Pr.10 DC injection brake operation frequency or less to when
the zero speed control or the servo lock operation starts in the Pr.1072 DC brake judgment time for anti-sway control
operation.
Frequency command
NOTE
• During anti-sway control operation, even if the motor rotation is restricted to one direction in the Pr.78 Reverse rotation
prevention selection, the motor may rotate in a direction opposite to the setting.
• A protective function (E.OSD) may be activated during vibration control. When using anti-sway control, set Pr.690
Deceleration check time = "9999 (initial value)" to disable the deceleration check function.
• When anti-sway control is enabled, regeneration avoidance, shortest acceleration/deceleration, and the traverse function are
disabled.
• Do not set anti-sway control and droop control together.
Parameters referred to
Pr.10 DC injection brake operation
Pr.78 Reverse rotation prevention
Pr.286 Droop
gainpage 738
Pr.292 Automatic
Pr.592 Traverse function
Pr.690 Deceleration check
Pr.875 Fault
definitionpage 422
Pr.882 Regeneration avoidance operation

5.14.9 Orientation control

Magnetic flux Vector
V/F
V/F
V/F
Magnetic flux
Magnetic flux
The inverter can adjust the stop position (Orientation control) using a position detector (encoder) attached to a place such as
the main shaft of the machine.
A Vector control compatible option is required.
Because Pr.350 Stop position command selection is initially set to "9999", the orientation control function is invalid.
Pr.
350
Stop position
*1
command selection
A510
351
Orientation speed
*1
A526
352
Creep speed
*1
A527
353
Creep switchover
*1
position
A528
Downloaded from
ManualsNet.com
STF
ON
frequencypage 715
selectionpage 406
acceleration/decelerationpage 384
selectionpage 582
timepage 269
selectionpage 732
Vector
Vector
Initial
Name
value
9999
2 Hz
0.5 Hz
511
search engine
Frequency command of anti-sway control
Pr.1072
Setting
range
0
Internal stop position command (Pr.356)
1
External stop position command (FR-A8AX 16-bit data)
9999
Orientation control disabled
0 to 30 Hz
Turning ON the X22 signal decelerates the motor speed to the set value.
0 to 10 Hz
After the speed reaches the orientation speed, the speed decreases to the
creep speed set in Pr.352 as soon as the current position pulse reaches the
creep switchover position set in Pr.353.
0 to 16383
Actual rotation
Pr.10 DC injection brake
operation frequency
Time
Zero speed control
Servo lock
Description
5.14 (A) Application parameters
1
2
3
4
5
6
7
8
9
10
585
5. PARAMETERS