Hitachi PC-ARFG-E Installation & Operation Manual page 60

Wired remote controller
Hide thumbs Also See for PC-ARFG-E:
Table of Contents

Advertisement

SERVICE & INSTALLATION MENU
Element
Optional function
KPI: Pre-cooling / pre-heating
period
E4
Econofresh: CO
sensor
2
Not used
Only for DX-Interface,
E5
KPI-E4E and KPI-X4E:
High ventilation after switch
ON
Period of indoor fan operation
E6
after cooling operation
stoppage
E7
Not used
Control for stop of the indoor
unit fan during heating
Thermo-OFF conditions (with
E8
remote sensor THM-R2AE
connected to the THM4
connector in the indoor unit
PCB)
E9
Not used
EA
Not used
Indoor unit fan control
Eb
during cooling Thermo-OFF
conditions
Forced Thermo-ON when
EC
stopping in cooling operation
Ed
Not used
Control in "Automatic" indoor
EE
fan speed mode
46
PMML0565 rev.1 - 04/2022
Individual
Settings
setting
00
Disabled (factory setting)
01
30 minutes
O
02
60 minutes
00
Disabled (factory setting)
01/02
CO
2
00
-
01
00
Disabled (factory setting)
01
60 minutes
00
Disabled function (factory setting)
O
01
60 minutes
02
120 minutes
00
-
01
00
Fan operation in Low speed
O
01
Fan stop in Thermo-OFF conditions.
00
-
01
00
01
-
02
00
Function disabled (factory setting)
O
01
Low
02
Slow
00
Function disabled (factory setting)
O
01
Enabled
00
O
-
01
00
Function disabled (factory setting)
O
01
Enabled
Setting conditions
sensor (required setting E1=00)
Description
This function delays unit startup
with energy recovery
This function selects the CO
2
gas sensor input for Econofresh.
Use at 00 conditions
This function forces that the unit
will operate in high speed during
60 minutes after fan start. After
this time the fan will be changed
to setting value.
This function prevents the
condensation in the unit by
keeping the fan running after the
unit operation has been turned
OFF.
Use at 00 conditions
This function stops the fan
to prevent cold draughts or
overheating.
C8 must be set to 01 to use the
E8=01 setting.
The connection of a THM-R2AE
remote temperature sensor to
the THM4 port in the indoor unit
PCB is required. The remote
sensor shall be installed in a
proper place for the correct
detection of room temperature.
(In case that automatic louver
is set, the louver will keep
operating in both Thermo-ON
and Thermo-OFF condition)
Use at 00 conditions
Use at 00 conditions
This function decreases speed
of the indoor unit fan during
cooling Thermo-OFF, to reduce
the spread of smells and
humidity.
This function is used to force
Thermo-ON during 6 minutes
when stopping in cooling
operation.
Use at 00 conditions
This function limits the speed
of the indoor fan when room
temperature is close to the
setting temperature.