Replacement Of The Stop Valve (With Check Joint); Replacement Of The High Pressure Switch (Psh); Replacement Of The Pressure Sensor (Pd); Replacement Of The Pressure Sensor (Ps) - Hitachi SAMURAI Series Service Manual

Condenserless water chillers
Hide thumbs Also See for SAMURAI Series:
Table of Contents

Advertisement

3. Servicing
Cycle components

3.3.8 Replacement of the stop valve (with check joint)

1 Remove the brazed parts using a blowtorch and 
previously  cooling  the  pipe  side  and  the  stop 
valve unit with wet cloth in order to avoid braz-
ing material enter inside the pipes.

3.3.9 Replacement of the high pressure switch (PSH)

1 Disconnect the cables (9 and 10 of the Pressure 
switch from the E-box of the compressor termi-
nal board).
2 Remove  the  screw  of  the  clamp  that  fixes  the 
switch.
3 Unscrew the switch and proceed to its replace-
ment
4 When  reassembling  proceed  in  reverse  order 
than removing.

3.3.10 Replacement of the pressure sensor (Pd)

1 Disconnect  the  cables  (4,  5  and  6  of  the  pres-
sure  sensor  from  the  E-box  of  the  compressor 
terminal board).
2 Remove  the  screw  of  the  clamp  that  fixes  the 
switch.
3 Unscrew the switch and proceed to its replace-
ment
4 When  reassembling  proceed  in  reverse  order 
than removing.

3.3.11 Replacement of the pressure sensor (Ps)

1 Disconnect the cables (1, 2 and 3 of the Pres-
sure  sensor  from  the  E-box  of  the  compressor 
terminal board).
2 Unscrew the sensor and proceed to its replace-
ment
3 When  reassembling  proceed  in  reverse  order 
than removing.
73
SMGB0097 rev.0 - 07/2015
Stop valve
Brazed parts
Screw
Screw
High pressure 
sensor (Pd)
Pressure sensor
(PS)
Check joint
High pressure 
switch (PSH)
Clamp
Clamp
3