4. Troubleshooting
Troubleshooting by alarm code
11-11
Alarm code
Alarm stop reason
Thermistor for detection of inlet water temperature (Twi) indicates an abnormal value.
PCB monitoring position
PCBc (CPU PCB) CN4 (Inlet water temperature thermistor (Twi))
N O T E
Refer thermistor characteristics chapter.
The connection and insertion of the connector 
CN4 on PCBc (CPU PCB) is correct
Remove the connector and measure the resist-
ance value. Is the resistance value normal?
12-12
Alarm code
C1-12
Alarm stop reason
Thermistor for detection of outlet water temperature (for water temperature control Two1) indicates an abnormal value.
PCB monitoring position
PCB
 (CPU PCB) CN5 (Outlet water temperature thermistor (Two1))
c
N O T E
Refer thermistor characteristics chapter.
The connection and insertion of the connector 
CN5 on PCBc (CPU PCB) is correct
Remove the connector and measure the resist-
ance value. Is the resistance value normal?
115
SMGB0097 rev.0 - 07/2015
Inlet water temperature abnormality (CN4)
No
Yes
No
Yes
Outlet water temperature THM abnormality (CN5)
No
Yes
No
Yes
Revision of connections
Replacement of thermistor
Replacement of PCBc 
(CPU PCB)
Revision of connections
Replacement of thermistor
Replacement of PCBc 
(CPU PCB)