2. Control Functions

Run operation

2.4 Run operation

2.4.1 Setting of switches on the setting PCB

1 Pump operation switch
By  setting  the  switch  ON  while  the  module  is  stopped, 
pump operation order is output.
2 Local / Remote switch
Switches  whether  the  operation  control  of  the  module 
is  performed  locally  or  remotely.  By  setting  it  to  local 
for  instance  during  inspection  or  maintenance  works, 
an  alarm  is  output  to  the  remote  side  in  case  that  any 
operation order was input remotely.
3 ON - OFF button
Performs as ON button for operation when in local control 
setting. The OFF button is always enabled, regardless of 
local/remote setting.
When  OFF  button  is  pushed  the  module  is  detached 
from  the  group.  The  rest  of  the  modules  will  keep 
operation  according  to  the  master  module  settings  and 
input conditions.
When  pushing  ON  button  the  module  recovers  the 
operation  on  the  group  and  restarts  the  operation 
according to the needs of the system.
50
SMGB0097 rev.0 - 07/2015
Pump Operation
ON
OFF
Local
Remote
SW2