Sizing; Derating; Cooling Air Flow Requirements - ABB ACS355 Series Supplement Manual

Drives with ip66/67 / ul type 4x enclosure (0.37...7.5 kw, 0.5...10 hp)
Hide thumbs Also See for ACS355 Series:
Table of Contents

Advertisement

Sizing

The current ratings are the same regardless of the supply voltage within one voltage range. To achieve
the rated motor power given in the table, the rated current of the drive must be higher than or equal to
the rated motor current.
Note 1: The maximum allowed motor shaft power is limited to 1.5 · P
torque and current are automatically restricted. The function protects the input bridge of the drive
against overload.
Note 2: The ratings apply at ambient temperature of 40°C (104°F).

Derating

The load capacity decreases if the installation site ambient temperature exceeds 40°C (104°F) or if the
altitude exceeds 1000 meters (3300 ft). Derating is not allowed.

Cooling air flow requirements

The table below specifies the heat dissipation in the main circuit at nominal load and
in the control circuit with minimum load (I/O and panel not in use) and maximum load
(all digital inputs in the on state and the panel, fieldbus and fan in use). The total heat
dissipation is the sum of the heat dissipation in the main and control circuits.
Type
ACS355...
(+B063)
x = E/U
3-phase U
03x-02A4-2
03x-03A5-2
03x-04A7-2
03x-06A7-2
03x-07A5-2
03x-09A8-2
03x-13A3-2
03x-17A6-2
3-phase U
03x-01A2-4
03x-01A9-4
03x-02A4-4
03x-03A3-4
03x-04A1-4
03x-05A6-4
03x-07A3-4
03x-08A8-4
03x-12A5-4
03x-15A6-4
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Main circuit
Rated I
and I
1N
2N
W
BTU/Hr
= 200...240 V (200, 208, 220, 230, 240 V)
N
19
65
31
106
38
130
60
205
62
212
83
283
112
383
152
519
= 380...480 V (380, 400, 415, 440, 460, 480 V)
N
11
38
16
55
21
72
31
106
40
137
61
208
74
253
94
321
130
444
173
591
Heat dissipation
Control circuit
Min
W
BTU/Hr
W
6.1
21
22.7
6.1
21
22.7
9.5
32
26.4
9.5
32
26.4
9.5
32
26.4
10.5
36
27.5
10.5
36
27.5
10.5
36
27.5
6.6
23
24.4
6.6
23
24.4
9.8
33
28.7
9.8
33
28.7
9.8
33
28.7
9.8
33
28.7
14.1
48
32.7
14.1
48
32.7
12.0
41
31.2
12.0
41
31.2
. If the limit is exceeded, motor
N
Air flow
Max
3
BTU/Hr
m
/h
ft
78
-
78
-
90
-
90
-
90
-
94
-
94
-
94
-
83
-
83
-
98
-
98
-
98
-
98
-
112
-
112
-
107
-
107
-
00353783.xls G
Technical data
51
3
/min
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs355-03e-08a8-4+b063

Table of Contents