Mounting, dismounting and electric installation

10.5.1 External power supply unit

The voltage is supplied via the PELV power supply units with safe
separation acc. to EN 50178 and EN 60950-1.
All control components are supplied from 24 V voltage supplies.
Use the Bosch Rexroth power supply unit VAP01.1H-W23-024-010-NN, part num-
ber R911171065, for the logic supply. For further information on the external
power supply unit and on the creation of overvoltage categories, refer to the
documentation of the power supply unit (refer to
ments" on page
2).
All lines of the 24 V voltage supply have to be routed separately from lines carry-
ing higher voltages.
All peripherals, such as digital sensors or actuators connected to the interfaces
of the control, also have to comply with the criteria of safety-separated circuits.
The same external power supply unit has to supply the 24 V voltage
supply of the XMx control and the extension modules. Bridge the ca-
bles between the power connectors XD1.

10.5.2 Voltage supply for the control and for the extension modules

The voltage supply for the control and the extension modules is supplied via the
XD1 plug.
Connect the power connector with cables with a conductor cross-
section of AWG 16-22 (0.34 mm
Use only copper cables for the connection.
Use only cables designed for ≥75 °C.
Observe the color-coding of the plugs.
Only the "XA-CN01" power connector is permitted to connect the 24
V supply voltage (see
page
8).
Bosch Rexroth AG R911376654_Edition 04
IndraControl XFE01.1-SY-01 Safety Ex-
chapter 1.5 "Related docu-
- 1.5 mm
2
chapter 5 "Spare parts and accessories" on
tension Module
).