Chapter 6. BUFFER MEMORY CONFIGURATION AND FUNCTIONS
Chapter 6. BUFFER MEMORY CONFIGURATION AND FUNCTIONS
The D/A conversion module has the buffer memory for communication of data with the PLC CPU.
6.1 Buffer Memory Configuration
This shows buffer memory configuration.
Address
G3F-DA3V
G4F-DA2V
G4F-DA3V
G6F-DA2V
(decimal)
0
1
2
3
4
-
5
-
6
-
7
-
The buffer memory of G3F-DA3V, G3F-DA3I, G4F-DA3V and G4F-DA3I are same. And the buffer memory of G4F-
DA2V, G6F-DA2V, G4F-DA2I and G6F-DA2I are same.
6.2 Buffer Memory Function
Each address of buffer memory has been occupied by one word, and it is displayed as 16 Bit.
Each address is composed of 16 Bit, and each Bit can be executed by specifying Bit on to 1 or Bit off to 0.
1) Digital input value can be used within the range 0 to 4000.
2) When digital input value isn't set, digital input value has to be set as follows.
Voltage output(G4F-DA3V/G4F-DA2V/G6F-DA2V) : 2000
Current output(G3F-DA3I/G4F-DA3I/G4F-DA2I/G6F-DA2I) : 0
Voltage output(G3F-DA3V) : 0
G3F-DA3I
G4F-DA2I
Descriptions
G4F-DA3I
G6F-DA2I
Digital input value
specification to channel 0
Digital input value
specification to channel 1
Digital input value
specification to channel 2
Digital input value
specification to channel 3
Digital input value
-
specification to channel 4
Digital input value
-
specification to channel 5
Digital input value
-
specification to channel 6
Digital input value
-
specification to channel 7
6 - 1
Detail
Non-initialization
Descriptions
G4F-DA3V / G4F-DA2V
/ G6F-DA2V :
Specify digital
Digital data is specified
data for D/A
to "2000".
conversion to
G4F-DA3I / G4F-DA2I /
these areas.
G6F-DA2I / G3F-DA3I /
(-48~4047)
G3F-DA3V:
Digital data is specified
to "0".
Remarks
R/W
"
"
"
"
"
"
"