LG MASTER-K200S Series User Manual page 41

Programmable logic controller
Hide thumbs Also See for MASTER-K200S Series:
Table of Contents

Advertisement

Chapter 8. MK PROGRAMMING
6.2.3
Programming for Mounting D/A Conversion Module on Remote I/O Station
This is programming for output D/A conversion value set by digital switch.
1) System Configuration
GM4-
K4P -
PA1A
15AS
2) Initial Settings
(1) Enabled channel : channel 0,
3) Descriptions of the Program
(1) P0020 turning On leads to displaying D/A conversion value set by digital switch on channel 0.
4) Program
P0020
M0200
G4L-
G4I-
G4I-
FUEA
D22A
D22A
(P0020)
digital switch
(P0010 ~ P001F)
[ <= D0100 4000 ]
If the BCD digital switch value is equal to or less than 4000 M200 is turned ON
[ RPUT
hC000
D0000 ]
Writing the values stored in D100 to buffer memory of address 0
8 - 6
Remote
Station
No."11"(0Bh)
GM4-
G4L-
G4F-
PA1A
RBEA
DA2V
[ DBINP
P001
D0100 ]
Storing the BCD digital value to D100
(OUT M0200)
h000B
D0100
00000
[ END ]
00001

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents