IndraControl XFE01.1-SY-01 Safety Ex-
tension Module
Mounting rail
●
Mount the extension modules on a 35 mm standard mounting rail. The
preferred overall height of the mounting rail is 7.5 mm (corresponds to TH
35-7.5 acc. to EN 60715).
Mount the extension module as described in this chapter.
The fastening distance of the mounting rails may not exceed 200 mm. This
distance is required to ensure stability while mounting and demounting the
control or the IndraControl extension modules
Fig. 10-2: Mounting rail fastening (in mm)
NOTICE
If screws and rivets are too high on the mounting rail, the bus base modules
do not really engage on the mounting rail. Use only screws and rivets with a
structural height of up to 3 mm to fasten the mounting rail.
End clamps
●
Fasten end clamps on both sides of the IndraControl XM station. End clamps
guarantee the correct fastening of the control and the modules connected to
them on the mounting rail and they are used as lateral end elements
Do not wire cables parallel to motor cables over a long distance or other
●
strong interference sources to avoid coupling of interferences
The LED displays may not be hidden
●
Wire all connecting cables in loops
●
Use strain reliefs for all cables
●
Keep the maximum distance possible from interference sources
●
Ensure the minimum distances for sufficient ventilation as specified in the
●
operating instructions of the XM control. (refer to
documents" on page
In case of a several line design, the supply air has to be measured under each
line and its limit value has to be observed. For information on ambient
temperatures, refer to
Additionally, provide sufficient distance for mounting, demounting, plugs and
●
cables
Mounting, demounting and electric installation
Electronic damage due to fastening elements
of the mounting rail
2)
chapter 6 "Ambient conditions" on page 8
_
< 200
chapter 1.5
R911376654_Edition 03 Bosch Rexroth AG
23/45
"Related