12/45
Technical data
Nominal voltage
Residual ripple
U
Lmax
U
Lmin
Maximum current consumption of the module from
U
at nominal voltage
L
Tab. 7-1: Operating voltage and current consumption IndraControl XFE01.1-SY-01
NOTICE
Ensure that the voltages remain in the specified range.

7.2 Safety-related characteristic values

Safety integrity level SIL
Performance level PL
Hardware error tolerance
Category
PFH (average frequency of a dangerous failure per
hour)
PFD
(average probability of a dangerous failure
avg
in case of request)
Service life T
M
MTTF
(mean time to failure)
d
DC
(average diagnostic coverage)
avg
Types of failure

7.3 Dimensions and weight

Dimensions (W × H × D)
Weight (without packaging)
Bosch Rexroth AG R911376654_Edition 03
IndraControl XFE01.1-SY-01 Safety Ex-
24 V DC +20%, -15%, PELV
±5 %
30 V
19.2 V
0.2 A
The Safety extension module IndraControl
XFE01.1-SY-01 goes into a safe state in case of
undervoltage or overvoltage
SIL3 (DIN EN 61508 and DIN EN 61131-6)
PL e (DIN EN ISO 13849-1)
HFT = 1
Category 4 (DIN EN ISO 13849-1)
4.5 × 10
-10
1/h
3.9 × 10
-5
20 years (DIN EN ISO 13849); no proof test
required
2,500 years
99 % ≙ high
If the internal diagnostics of the Safety extension
module IndraControl XFE01.1-SY-01 detects an
error, the module goes into the safe state, that is,
no more safe bus telegrams are sent
35 × 122.4 × 95.8 mm
200 g
tension Module