Timing Depending On The Position Of Rotary Switch S1 And Settings In The Ups-Nt Control Software - Bosch Rexroth IndraControl VAU 01.1U Project Planning Manual

Vau 01.1u ups with usb interface
Hide thumbs Also See for Rexroth IndraControl VAU 01.1U:
Table of Contents

Advertisement

DOK-SUPPL*-VAU*01.1U**-PR03-EN-P
Rexroth IndraControl VAU 01.1U UPS with USB interface
Switch position 4 to 7 (for commis‐
sioning)
Switch position 0
Switch position 1
Switch position 2
Switch position 3
Switch position 4
Switch position 5
Switch position 6
Switch position 7
6.4.4
Timing Depending on the Position of Rotary Switch S1 and Settings in
the UPS-NT Control Software
Overview
Switch position
0
1
2
3
Fig.6-4:
Switch position 0 to 3
If switch positions 4 to 7 are used, the timer (time delay of 120 sceonds) inte‐
grated in the UPS is switched off. Thus, unnecessary waiting times, e.g. dur‐
ing commissioning, are avoided. After commissioning reset the switch to the
switch positions 0 to 3.
We recommend switch positions 4 to 7 exclusively for commis‐
sioning to avoid waiting times.
Switch position
4
5
6
7
Fig.6-5:
Switch position 4 to 7
If the rotary switch is set to 0, UPS operation is 5 seconds with a time delay
of 120 seconds.
If the rotary switch is set to 1, UPS operation is 60 seconds with a time delay
of 120 seconds.
If the rotary switch is set to 2, UPS operation is 120 seconds with a time de‐
lay of 120 seconds.
If the rotary switch is set to 3, UPS operation is 180 seconds with a time de‐
lay of 120 seconds.
If the rotary switch is set to 4, UPS operation is 5 seconds without time delay.
If the rotary switch is set to 5, UPS operation is 60 seconds without time de‐
lay.
If the rotary switch is set to 6, UPS operation is 120 seconds without time de‐
lay.
If the rotary switch is set to 7, UPS operation is 180 seconds without time de‐
lay.
For further information on the UPS-NT Control software, please refer to the
relevant documentation of the connected device, see also
mitted Devices" on page
6.
Example: Switch position 2, Shutdown Delay Time = 45 seconds
Bosch Rexroth AG
Operating and Display Components
UPS time
5 seconds
60 seconds
120 seconds
180 seconds
UPS time
5 seconds
60 seconds
120 seconds
180 seconds