Download Print this page

Bosch C900V2 Quick Start Manual page 2

Dialer capture module
Hide thumbs Also See for C900V2:

Advertisement

6
6
Confi gure the Dialer Protocol
Locate DIP switches 1 through 10 and set all switches OFF.
Locate the illustration below that matches the dialer format for
your control panel and set the appropriate switches ON.
1
2
3
4
5
6
7
8
9
10
ADT-SIA
Set switches 1, 2, 3, and 10 ON.
1
2
3
4
5
6
7
8
9
10
BFSK (1400 Hz ACK Tone)
Set switches 2, 4, and 10 ON.
1
2
3
4
5
6
7
8
9
10
BFSK (2300 Hz ACK Tone)
Set switches 2 and 10 ON.
DTMF (Includes Contact ID,
1
2
3
4
5
6
7
8
9
10
High Speed, and 4/2 Express)
Set switches 3 and 10 ON.
DTMF (where dialer retransmits
1
2
3
4
5
6
7
8
9
10
quickly - includes Contact ID, High
Speed, and 4/2 Express)
Set switches 3, 4, and 10 ON.
FBI Superfast DTMF
1
2
3
4
5
6
7
8
9
10
(1400 Hz ACK Tone)
Set switches 2, 3, 4, and 10 ON.
FBI Superfast DTMF
1
2
3
4
5
6
7
8
9
10
(2300 Hz ACK Tone)
Set switches 2, 3, and 10 ON.
Pulse 3/1, 3/1 Checksum
1
2
3
4
5
6
7
8
9
10
(1400 Hz ACK Tone)
Set switches 1, 4, and 10 ON.
Pulse 3/1, 3/1 Checksum
1
2
3
4
5
6
7
8
9
10
(2300 Hz ACK Tone)
Set switches 1 and 10 ON.
Pulse 4/2
1
2
3
4
5
6
7
8
9
10
(Long 1400 Hz ACK Tone)
Set switches 1, 3, 4, and 10 ON.
OFF ON
1
2
3
4
5
6
7
8
9
10
Pulse 4/2
1
2
3
4
5
6
7
8
9
10
(Long 2300 Hz ACK Tone)
Set switches 1, 3, and 10 ON.
1
2
3
4
5
6
7
8
9
10
Radionics Modem II
Set switches 4 and 10 ON.
Radionics Modem IIe and
1
2
3
4
5
6
7
8
9
10
2
Modem IIIa
Set switch 10 ON.
1
2
3
4
5
6
7
8
9
10
Robofon
Set switches 2, 3, and 4 ON.
1
2
3
4
5
6
7
8
9
10
Seriee DTMF
Set switches 1, 2, and 3 ON.
1
2
3
4
5
6
7
8
9
10
Seriee FSK
Set switches 1, 2, 3, and 4 ON.
SIA Bell 103
1
2
3
4
5
6
7
8
9
10
(110/300 baud, 2016 Hz ACK Tone)
Set switches 1, 2, and 10 ON.
SIA Bell 103
1
2
3
4
5
6
7
8
9
10
(110/300 baud, 2083 Hz ACK Tone)
Set switches 1 and 2 ON.
1
2
3
4
5
6
7
8
9
10
SIA V.21 (110/300 baud)
Set switches 1, 2, and 4 ON.
1
2
3
4
5
6
7
8
9
10
Telim
Set switches 2 and 3 ON.
7
7
Connect Local Telephone
L
H
L
H
BOSCH
2003
BOSCH
2003
34296K
V1.11
34296K
000000AA
V1.11
000000AA
Connect the telephone to
No telephone
the C900V2 TELCO jack.
connection
Set switch 5 ON.
Set switch 6 ON.
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
Set Supervision
8
8
Poll Period
Set the poll period for your central station (Step 1).
75 seconds
240 seconds
Set switches 8 and 9 ON.
Set switches 7, 8, and 9 ON.
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
9
Connect to Power Supply
Control Panel
C900V2
L
H
BOSCH
2003
34296K
V1.11
000000AA
-
+
1. Connect the +V and –V terminals
on the C900V2 to the appropriate
terminals on the control panel.
2. Connect the C900V2 ground
terminal to earth ground in the
+
control panel enclosure.
3. Reconnect power to the control
panel.
10
10
Confi gure Using the Web
L
H
BOSCH
2003
34296K
V1.11
000000AA
C900V2
Router
Use your computer's web browser to visit
9
10
www.c900v2.com
Follow the instructions to initialize your central station
account.
Use your application ID number from Step 1.
1
1 1 1
Check Status
L
H
9
10
BOSCH
2003
34296K
V1.11
000000AA
System
Dialer
The System LED should be fl ashing green at 5 Hz.
The Dialer LED should be solid green.
Verify that the control panel is under central station
supervision by generating a test message from the control
panel.
Confi rm that the central station received the test message.
Installation Complete
© 2005 Bosch Security Systems
F01U013273B
2