STEP 4
With the G7 stopped, turn on auto tuning.
F400
Program
Motor
Parameters
Model
STEP 5
Place the G7 in local mode. Close S4 (E-Stop) and ST (Standby).
Give the G7 a frequency command of 1 .OHz.
Press the Start Button
Observe the display while the drive autotunes.
CAUTION: AFTER TUNING, THE G7 WILL ACCELERATE THE MOTOR TO THE FREQUENCY
SETPOINT
Go to monitor and observe excitation current and torque current.
Go to the 'Vector Motor Model' Parameter screen and record the values for
PRIMARY_________ RESISTANCE SECONDARY______________ RESISTANCE EXCITATION
INDUCTANCE___________
Are these values different from those previously recorded?
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192
efesotomasyon.com -Toshiba inverter,drive,servo,plc
Autotune
Vector
Motor
Select 'Enable Autotune on Run
Command'. The G7 will use the
algorithm saved in memory
this motor model.
for
38