Toshiba G7 Series Applications Workbook page 29

Hide thumbs Also See for G7 Series:

Advertisement

Programming
Direct
Parameter Path
Access
F004
Program
Fundamental
Parameters
F207
Program
Fundamental
Parameters
F115
Program
Terminal Selection
Parameters
F200
Program
Fundamental
Parameters
(27) Place G7 in remote control mode
(28) Close F to CC terminal
(29) With the S1 to CC open, the drive will follow the frequency input from RR input
(30) Close S1 to CC terminal
(31) The drive will now follow the II input for its speed reference
Method 2 -
In this example, RR input is programmed as Frequency mode #1 and II as the #2. Connection will be
the same as the example above but without the use of S1 input.
Programming
Direct
Parameter Path
Access
F004
Program
Fundamental
Parameters
F207
Program
Fundamental
Parameters
F208
Program
Fundamental
Parameters
F200
Program
Fundamental
Parameters
(1) Place G7 in remote control mode
(2) Close F to CC terminal
(3) With the RR input down below 5 VDC (30 hz), the drive follows the II input anywhere in the frequency span
(4) When the RR input is above 5 VDC (30 hz), the drive now follows the RR in the range of 30 – 60 hz regardless of the II input
(5) When the RR input is below 5 VDC (30 hz) again, the drive follows the II input
(6) If the F200 parameter is set to Frequency Source #2 Priority, the reverse will be true for the above example
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192
efesotomasyon.com -Toshiba inverter,drive,servo,plc
Standard Mode Selection
Standard Mode Selection
Input Terminal Function
Standard Mode Selection
Standard Mode Selection
Standard Mode Selection
Standard Mode Selection
Standard Mode Selection
Parameter Name
Frequency Mode #1
Frequency Mode #2
S1
Reference Priority
Selection
Parameter Name
Frequency Mode #1
Frequency Mode #2
Mode #1/#2 Switching
Frequency
Reference Priority
Selection
Comments
Use RR
Use VI/II
Set to 52 as Frequency Priority
Set to Frequency Source Priority Switching
Comments
Use RR
Use VI/II
Set to 30 hz
Set to Frequency Source #1 Priority
29