Advertisement

Commissioning

6.4 Modbus address register

4. Check the device parameters and adjust them if necessary.
Note
You can only change parameters in offline mode.
You can find more information on parameterization in the powerconfig Online Help.
5. In the "Parameters" window, click the "Load to device" button.
The set parameters are loaded to the device.
6.4
Modbus address register
6.4.1

Modbus address table for single-phase devices with Modbus interface

Continuous measured values
Modbus measured variables with the function codes 03 and 04
Address
Number
of regis-
Hex
Decimal
ters
0002
2
2
0004
4
2
0006
6
2
0008
8
2
000A
10
2
000C
12
2
000E
14
2
0010
16
2
0012
18
2
0014
20
2
0016
22
2
0018
24
2
001A
26
2
Range limit
0026
38
2
Range limit
0032
50
2
82
Format
Access
Unit
UINT32
R
V
UINT32
R
A
INT32
R
W
INT32
R
var
INT32
R
INT32
R
Hz
Factor
Measured variable
0.01
Voltage
0.001
Current
10.0
Active power
10.0
Reactive power
0.01
Power factor
0.1
Frequency
Equipment Manual, 09/2020, 2514284147-04
7KT16 energy meter