ABB RELION REB500 Operation Manual

ABB RELION REB500 Operation Manual

Distributed busbar protection, version 8.3 iec
Hide thumbs Also See for RELION REB500:
Table of Contents

Advertisement

Quick Links

®
RELION
REB500
Distributed busbar protection REB500
Version 8.3 IEC
Operation manual
/t1ain m1:nu
Events
Measu remen ts
Distu rbance records
Settings
10:5 3:.10
2013 -03- 30
joi,je ct name
j$sup erUs er
=
/Main menu
a
I
;
D
-
i!9?
t�, �
;;: ::
J
e
Setti rlgS
conf i� ation
rua,gr,o stics
rests
O•�
L¥19"39f�
; =
=
I D I
D
D

Advertisement

Table of Contents
loading

Summary of Contents for ABB RELION REB500

  • Page 1 ® RELION REB500 Distributed busbar protection REB500 Version 8.3 IEC Operation manual /t1ain m1:nu /Main menu i!9? Events t�, � ;;: :: Measu remen ts Distu rbance records Setti rlgS Settings conf i� ation rua,gr,o stics rests O•� L¥19"39f� joi,je ct name j$sup erUs er 10:5 3:.10 2013 -03- 30...
  • Page 3 Disturbance records SettirlgS Settings confi� ation rua,gr,o stics rests O•� L¥19"39f� joi,ject name j$superUs er 3:.10 2013-03- 3010:5 I D I Document ID: 1MRK 500 132-UEN Issued: May 2019 Revision: B Product version: 8.3 © Copyright 2019 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license.
  • Page 5 This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
  • Page 6 (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Detailed view (Open window)...................27 4.5.7.4 Disturbance recorder file (Detailed view/ Upload )............. 27 4.5.8 Event list.............................28 4.5.8.1 Classification of events..................... 28 4.5.8.2 Load events..........................29 4.5.8.3 Deleting events........................29 Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 8 Analogue inputs........................56 4.6.8.2 Recording..........................57 4.6.8.3 Signals........................... 57 Settings menu..........................61 Testing menu..........................62 4.8.1 Test mode..........................62 4.8.1.1 Using the test generator....................63 4.8.1.2 Shutting down the test generator.................. 64 Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 9 Accessing the WebHMI......................87 Section 7 Troubleshooting...................89 Safety Instructions........................89 List of faults and corrective actions..................89 7.2.1 Useful LEDs on the IEDs and switches................89 7.2.1.1 Switches..........................89 Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 10 Faults during startup......................90 7.2.3 Alarm and Event list entries....................91 7.2.4 Optical fiber connections faults.................... 91 7.2.5 Electrical connection faults....................92 Diagnostic (DIA) system - error handling................92 Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 11: Introduction

    Getting started guide 1MRK 505 404-UEN Symbols and conventions 1.4.1 Symbols GUID-4F7DD10A-DEE5-4297-8697-B8AAB5E3262F v2 The electrical warning icon indicates the presence of a hazard which could result in electrical shock. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 12: Document Conventions

    For example, the default value of the • Section references are presented with the respective section numbers. For example, see Section 1.4.2 for more details about document conventions. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 13: Safety Information

    Non-observance can result in death, personal injury or substantial property damage. Only a competent electrician is allowed to carry out the electrical installation. National and local electrical safety regulations must always be followed. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 14 There is a danger of contact with live parts when opening REB500 cubicle doors. Electrostatic discharge can destroy components in the equipment. Other safety instructions pertaining to particular operations are contained in the respective chapters of the operating instructions. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 15: System Overview

    H el p M enu H el p M enu H el p Isolator Image Current inputs Trip CB output 12000185-IEC18000287-1-en.vsdx IEC18000287 V2 EN-US Figure 1: System overview Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 16 10 IP addresses will be assigned automatically, when connected. This functionality is available on the LHMI port only. Information on how to configure different IP-addresses can be found in Section 4.9.5.2. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 17: Hmi500

    Basic setup 4.3.1 Installation GUID-03F144BC-35AF-4F84-A0C8-120CD66B6FCA v2 The human-machine interface program HMI500 is supplied on an installation CD. It can be installed on Windows XP or Windows 7. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 18: Uninstallation

    The first screen to appear after starting the operator program is the System login dialog box: 15000019-IEC18000288-1-en.vsdx IEC18000288 V1 EN-US Figure 2: System login dialog box Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 19: Window Structure

    Close The window or dialog is closed and a warning is displayed, if changes have been made which have not been saved. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 20: Main Window

    Information details of the software version. Status information is displayed on the bar at the bottom of the main window as shown in Figure 12000074-IEC18000290-1-en.vsdx IEC18000290 V1 EN-US Figure 4: Status bar Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 21: File Menu

    Exit Terminates the program; displays a warning if there are changes that have not been saved. You then have the choice of saving or discarding them. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 22: Download To Protection System

    6. The correct time format must be set via the control panel on the PC for the procedure to be presented correctly. The procedure can be interrupted by the user as far as Archive data in the protection system. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 23: Compare

    GUID-8F72571E-75C1-46BC-807C-F8B16DFC9AAA v1 When selecting this menu item, the dialog box shown in Figure 7 appears. See Table 5 for an explanation of all items in this dialog box. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 24: View Menu

    4.5.1 Single-line diagram GUID-146BCC01-642D-4972-8FC7-16B550979035 v2 This menu item displays a diagram of the plant corresponding to the layout of the connection diagrams created by ABB. The screenshot in Figure 8 shows an example of a single-line diagram. Distributed busbar protection REB500 Operation manual ©...
  • Page 25 (see Figure 9). The buttons on the right provide facility for changing the default colors for open, closed or invalid objects to suit your needs. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 26: Protection Zone Measurements

    Protection zones that have been connected, for example, via a pair of feeder isolators or a longitudinal isolator, are also presented. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 27: Detailed View

    The differential current, the restraint current and the stability factor are also displayed. 12000083-IEC18000492-1-en.vsdx IEC18000492 V1 EN-US Figure 11: Detailed view of measurements per zone Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 28: Analogue Input Measurements

    Update cyclically. This updates all open status windows. A status window shows either inputs or outputs. Two windows can be opened to view the inputs and outputs of a bay at the same time. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 29: Switchgear Objects

    GUID-5EF660A7-0B9B-4131-8ED2-5819AD7A0C2C v1 The detailed view shows the statuses of circuit-breakers and isolators. If neither a closed nor an open position is defined, the status invalid is displayed. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 30: Protection Zone Circuit-Breakers

    IEC18000496 V1 EN-US Figure 15: Protection zone circuit-breakers, detailed view These circuit-breakers are intertripped, for example, in the event of a busbar fault in the respective protection zone. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 31: Disturbance Recorder

    Description Ready Disturbance recorder is ready to record disturbances. Memory full Disturbance recorder memory is full Not available Disturbance recorder function is not active for the bay Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 32: Upload Disturbance Recorder Records

    In case the maximum number of disturbance records has been reached, an ongoing upload of the oldest record could be interrupted by a trigger initiating a new recording. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 33: Detailed View (Open Window)

    Day of the recording (Trigger time) Hour of the recording (Trigger time) Minute of the recording (Trigger time) Second of the recording (Trigger time) Table continues on next page Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 34: Event List

    The mixed event list shows both, the entries of the normal and the extended view. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 35: Load Events

    Delete PC list. Deleting can take several seconds. 4.5.8.5 Deleting the system list GUID-15FBA23A-7AB5-4568-B541-6A1D45119A9F v1 All the events stored in the protection system are deleted. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 36: Deleting Events That Have Been Viewed

    This dialog has three tabs: Overview, Inputs, and Outputs. Table continues on next page Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 37: Communication

    In this window, all the event signals configured in the REB500 are displayed. For each event signal a user specific text can be configured (32 characters). The user can sort the list as per ABB reference or the standard text. LHMI LED…...
  • Page 38: Scs Diff Current Parameters

    Device structure GUID-7B9E243A-CAAC-4EBF-8914-C94DECD19692 v1 The device structure is configured by ABB when engineering the system. This dialog box is only for information as the configuration cannot be changed. The Overview tab lists the central unit and all the bay units along with their device label and device type.
  • Page 39: Binary Inputs/Outputs

    Figure 25: Configuration/ Binary module - Overview The Overview tab shows a list with all configured devices providing binary inputs/outputs. See Table 8 for an explanation of the columns. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 40: Inputs

    To configure a physical input as an event select it in the list and click on OC event config. to open the Configuration of events window. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 41 IEC18000538 V1 EN-US Figure 26: Configuration / Binary module - Central unit inputs 13000006-IEC18000539-1-en.vsdx IEC18000539 V1 EN-US Figure 27: Configuration / Binary module - Bay unit inputs Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 42: Inputs Details Tab

    CU and/or BU event memories. Furthermore, events can be assigned to the event lists of IEC 60870-5-103 interbay bus (IBB) 1 Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 43: Outputs

    Most of the CU signals only occur once. There is an output signal Trip BB zone for each section of busbar (bus zone), therefore the respective zone must be given when selecting this signal. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 44: Outputs Overview Tab

    For reasons of safety, it is impossible to mix tripping commands and signals, that is tripping commands can only be combined with tripping commands and control signals with control signals. Tripping commands: Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 45: Outputs Details Tab

    100 ms. 4.6.3.7 Outputs Details tab GUID-EE407B2E-94CC-47BF-9614-99402DCF88B1 v1 13000010-IEC18000542-1-en.vsdx IEC18000542 V1 EN-US Figure 32: Configuration/ Binary module/ Outputs/ Details - CU Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 46 Select an output relay in theoverview dialog box first by clicking on its label above the signal list (its column is then highlighted). Click CR event config to open the event configuration dialog box. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 47: Goose Input Support

    M enu H el p Line protection Line protection  CB fails  Line fault 15000036-IEC18000556-1-en.vsdx IEC18000556 V2 EN-US Figure 34: GOOSE input support - Information flow Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 48: Interface To System Engineering Tool

    Using GOOSE input signals for protection functions requires interaction between the REB500 configurator (HMI500) and the System engineering tool. Table 10 provides an overall view of the engineering process. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 49 HMI500 The available Configuration/Communication/SCS Configuration/IEC GOOSE data 61850-8-1 options/Import GOOSE data attributes button attributes are (see Figure 38). imported (from SCD file) Table continues on next page Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 50: Enabling Goose Client

    2 through 11. 4.6.4.2 Enabling GOOSE Client GUID-D2A41405-8484-45BC-B5E2-82EEE0FD8D9B v1 This section describes the pre-configuration of the GOOSE Client. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 51: Export Iid/Cid File

    Figure 36: Tools/ Export SCS data A successful export is indicated by the SCS data exported message box. Additionally the location of the configuration file is shown. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 52: Import Goose Attributes

    Delete GOOSE data attributes. A successful import is indicated by the GOOSE data attributes imported message box. The number of imported attributes is shown in the box. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 53: Goose Input Mapping

    Breaks the connection between the GOOSE data attribute and the REB500 input signal. The GOOSE data attribute can be assigned to another REB500 Signal. Selection – GOOSE data Table 12 attribute filter Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 54: Requirements To Goose Input Signals

    X1001 (PRP LineA) and X1002 (PRP LineB) respectively. Figure 42 illustrates a busbar fault and the resulting information (trip signal) flow assumed that the control IED receives the trip information by GOOSE. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 55 A high priority event is also created in case of a trip of the bay local protection functions that is BFP, EFP, BP, … . Combined tripping commands in the Technical Manual . See section Table continues on next page Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 56: Configure Goose Control Blocks

    Configure GOOSE control blocks GUID-C3D6214E-FD14-4C7F-B7CB-05578D815551 v1 This section describes the configuration of the GOOSE control block. Depending on the requirement up to 12 GOOSE control blocks can be defined. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 57 Figure 44: Configuration / SCS Configuration – IEC 61850-8-1 options / GCB configuration Fields of the GOOSE control blocks are used according to IEC 61850-7-2 and IEC 61850-8-1. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 58: Defining Signals For Goose Send

    Only specific Signals can be assigned to GOOSE. In the Details Tab of the Binary Module/ Outputs the menu item GOOSE control block assignment is only shown for these specific signals. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 59: Event Text Configuration

    In this window, all the event signals configured for REB500 are displayed. For each event signal, a user specific text can be defined (maximal 32 characters). The user can sort the list as per ABB reference or the standard text. 12000117-IEC18000509-1-en.vsdx...
  • Page 60: Lmi Leds

    A LED is assigned to a signal by marking it in the dialog and clicking on New signal or alternatively by double-clicking on the LED line. A list of possible signals is then presented to Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 61: Delete Signal

    Switch open green: For a defined ON or OFF state of a switch (breaker/ isolator binary input signals 0 1 or 1 0) the closed position is indicated by a red LED and the open position Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 62: Disturbance Recorder

    If in a protection zone only one phase measurement is valid, the value “0” is recorded. • The measuring range of the phase difference is 0 .. 3142 mrad (0° .. 180°). Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 63: Recording

    The overview shows all devices and their basic disturbance recorder configurations. A device is selected by clicking on it with the mouse. The column ABB ref. indicates an internal designation for the devices. The reference =ABB00 is always assigned to the central unit. The references =ABB01-xx are assigned to the bay units.
  • Page 64 The trigger inputs are scanned every 16 ms. A trigger signal must have a pulse duration of at least 16 ms to be certain that it will be detected. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 65 Section 4 HMI500 13000012-IEC18000544-1-en.vsdx IEC18000544 V1 EN-US Figure 51: Disturbance recorder – Configuration (Bay Unit) 15000033-IEC18000555-1-en.vsdx IEC18000555 V1 EN-US Figure 52: Disturbance recorder – Configuration (Central Unit) Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 66 Section 4 1MRK 500 132-UEN B HMI500 13000013-IEC18000545-1-en.vsdx IEC18000545 V1 EN-US Figure 53: Disturbance recorder/ Configuration/ Signals 13000014-IEC18000546-1-en.vsdx IEC18000546 V1 EN-US Figure 54: Disturbance recorder – Overview Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 67: Settings Menu

    Circuit-breakers ● Isolators Isolators ● Current transformers Current transformers ● Voltage transformers Voltage transformers ○ Busbar protection Busbar protection Busbar protection ● Table continues on next page Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 68: Testing Menu

    (has to be opened by the operator), (see Section 4.5.4). When the test generator is active, the statuses of the tripping commands cannot change. 12000095-IEC18000502-1-en.vsdx IEC18000502 V1 EN-US Figure 56: Test mode Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 69: Using The Test Generator

    Regardless of whether they are logical 0 or logical 1, inputs and outputs are normally green, those with impressed statuses yellow and invalid ones red. Impressed statuses are green after the display is refreshed. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 70: Shutting Down The Test Generator

    Installation mode dialog box opens. Click on Installation mode in the Testing menu to reset the installation mode. The tick in the menu item is reset. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 71: Tools Menu

    X . YY , date of the last change, description The version is purely numerical, that is X Version: (0...9) and Y (0...9). It is assigned by ABB while processing the contract and determined at the time the system is accepted by the user. The user cannot change it subsequently.
  • Page 72: File Verification

    File verification GUID-68B3B3E6-FF61-4B87-909C-1A5F1775B16E v1 Starts the file verification procedure, that checks data consistency within several tables of the project file. The result is displayed in a separate window. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 73: Reports

    Export button creates files that can be used to configure the communication interface at the remote end 4.9.5 Settings GUID-DB508E6C-93A9-4A69-B7AB-1B49379BD4CD v1 4.9.5.1 HMI500 settings GUID-9430004F-C808-43F7-8AFE-A21685142EFE v1 Some of the operator program functions can be customized. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 74: Communication

    DRR viewer support (optional) GUID-05DC846E-9C93-4C2A-B190-01F14AA177DC v2 HMI500 automatically displays the DRR viewer support tab when Wavewin ABB is installed on the PC (the version H.G.24 installation file is available on REB500 product CD). Use Select viewer button to change WaveWin ABB’s installation path if it has been changed or select the installation path of E_wineve (if installed and preferred).
  • Page 75: Security Account Management

    PC. The settings in the fields can be incremented or decremented by clicking on the appropriate arrow to the right of the value. Click on Set time to set the new date and time on the protection system. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 76 Section 4 1MRK 500 132-UEN B HMI500 12000105-IEC18000507-1-en.vsdx IEC18000507 V1 EN-US Figure 63: Setting the system time Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 77: Local Hmi

    There are different ways of viewing operating, disturbance and tripping data: • Local HMI • PC running HMI500 • Remote HMI • Station automation system (SCS) Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 78: Viewing Data On The Local Hmi

    IEC18000535 V1 EN-US Figure 64: Local human-machine-interface (LHMI) 5.3.3 Protection indicator LEDs GUID-7CDD0038-660F-451B-9001-B016322C63CA v1 There are three LEDs on top of the display: green, yellow, and red. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 79: Led Signals

    Certain LMI menus require a user authentication, for example, the LMI Test Trip menu requires a user login to access the menu. After a failed authentication this button re-opens the login window. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 80: Menu Structure

    • System Information • Station Name • System frequency • DB Version • Date of last DB change • Index to last DB change • LED Text Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 81: Menu Structure Of The Bay Unit

    • Reset all relays, lists and LEDs • Acknowledge Alarms • Reset Permanent Blocking • Reset blocking signals • Measurements • Currents • Voltages • Binary inputs Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 82 CPU Load • System Logger • Central unit • Measurements • Bus zones • Binary inputs • Binary outputs • Settings • System response • Busbar protection Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 83: Alarms

    • General alarm Viewing the event list and disturbance records is recommended should an alarm occur. The corresponding procedure is described in Section 4.5.7 Section 4.5.8 respectively. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 84: Trips

    2) Trip signals column is fixed on left side of the trip list 3) Value: information (number of columns) depends on the information content of the trip signal 4) Current value indications are generally instantaneous values Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 85: Test Trip

    To enter LHMI Test Trip menu a user authentication is mandatory in case that user account management is enabled. For details about the user account Cyber security guideline . management see Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 86: Configuration

    After configuring the LHMI Test Trip, the functionality can be used on a particular feeder’s LHMI. Use down and right arrow keys in the LHMI menu Test to find the Test Trip menu. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 87 Figure 66: LHMI Test Trip Menu The Test Trip menu can be entered by pressing the right arrow key, which opens first the logon window to authenticate the user (see Figure 67). Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 88 The sequence of characters may differ depending on the configured LHMI language. Each selected letter needs to be confirmed by pressing the right arrow key. To confirm the user name and/or password, press the Enter key. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 89 Test Trip (11115_Ext_Test_TRIP). In combination with the external Test Trip input, it might be ON state (if the state of input signal 11115_Ext_Test_TRIP is set to ON) . in the Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 90 Every requested Test Trip change requires a confirmation by the user. A cancellation of the initiated change is possible by navigation with the right arrow key to the Cancel menu item and pressing the Enter key. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 91 1MRK 500 132-UEN B Section 5 Local HMI 18000072-IEC19000211-1-en.vsdx IEC19000211 V1 EN-US Figure 70: LHMI Test Trip confirmation The following figure shows the LHMI Test Trip in active state. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 92 The Test Trip menu will be left automatically after the configured display timeout, which can be changed in the LHMI menu Display settings/LHMI/ Display Timeout. Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 93: Web Hmi

    To access the WebHMI, browse to the following URL via the station bus (LAN0): https://LAN_0_IP/reb500.html Information: Access to the WebHMI is protected by the user management. For required Cyber Security Deployment Guideline . permissions, see Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 95: Troubleshooting

    The Ready LED is on the top of the BU/CU. The Alarm Indicator LED is located in the right lower corner of the IED, integrated within the alarm button (see Section 5.3.3 Section 5.3.6). Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 96: Faults During Startup

    Check power supplies of LED On missing the Switch Wrong Ethernet Check Section 7.2.4 connect. between switches 14205_Block EFP Signal 11505_Close Configure signal 11505 always On command CB missing Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 97: Alarm And Event List Entries

    IEC 103 RX/TX LED dose Optical fiber defect, or wrong Check optical fibers not blink type Optical fiber wrong connection Check optical fiber connections Wrong IEC103 Configuration Check IEC103 Configuration Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 98: Electrical Connection Faults

    Repetitive BU Major_Error 021 3 per 600 sec In case of Repetitive BU restarts, the target blocks restarts permanently Table continues on next page Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 99 Event Detection Description setting Permanently Major_Error 176 If the error handling detects start-up or repetitive Blocked error causes (see Table 15), the permanently blocked state is set Distributed busbar protection REB500 Operation manual © Copyright 2019 ABB. All rights reserved...
  • Page 102 ABB AB Grid Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 Scan this QR code to visit our website www.abb.com/protection-control © Copyright 2019 ABB. All rights reserved.

Table of Contents