ABB RELION REB500 Product Manual

ABB RELION REB500 Product Manual

Distributed busbar protection version 8.3 iec
Hide thumbs Also See for RELION REB500:

Advertisement

®
RELION
REB500
Distributed busbar protection REB500
Version 8.3 IEC
Product guide
/t1ain m1:nu
Events
Measu remen ts
Distu rbance records
Settings
10:5 3:.10
2013 -03- 30
joi,je ct name
j$sup erUs er
=
/Main menu
a
I
;
D
-
i!9?
t�, �
;;: ::
J
e
Setti rlgS
conf i� ation
rua,gr,o stics
rests
O•�
L¥19"39f�
; =
=
I D I
D
D

Advertisement

Table of Contents
loading

Summary of Contents for ABB RELION REB500

  • Page 1 ® RELION REB500 Distributed busbar protection REB500 Version 8.3 IEC Product guide /t1ain m1:nu /Main menu i!9? Events t�, � ;;: :: Measu remen ts Distu rbance records Setti rlgS Settings conf i� ation rua,gr,o stics rests O•� L¥19"39f� joi,je ct name j$sup erUs er 10:5 3:.10 2013 -03- 30...
  • Page 2: Table Of Contents

    7. Requirements..............18 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. © Copyright 2019 ABB. All rights reserved.
  • Page 3: Application

    Petersen coils. Typical substation layouts GUID-5A26E5F0-2BA1-4EB5-ABC3-3A4A19EBF9E3 v1 17000003-IEC18000373-1-en.vsd IEC18000373 V1 EN-US Figure 1. Single busbar © Copyright 2019 ABB. All rights reserved...
  • Page 4 QB1 QB2 QB1 QB2 QB1 QB2 17000004-IEC18000374-1-en.vsd IEC18000374 V1 EN-US Figure 2. Double busbar QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 17000005-IEC18000375-1-en.vsd IEC18000375 V1 EN-US Figure 3. Triple busbar © Copyright 2019 ABB. All rights reserved...
  • Page 5 Distributed busbar protection REB500 1MRK 505 402-BEN B Version 8.3 IEC 17000006-IEC18000376-1-en.vsd IEC18000376 V1 EN-US Figure 4. 1 ½ breaker system © Copyright 2019 ABB. All rights reserved...
  • Page 6 ● Dynamic Busbar replica with display of currents ● Test generator for commissioning and maintenance ● Detached Local HMI ● Delay/Integrator function ● Binary logic and flip-flop functions ● (● standard, ○ optional) © Copyright 2019 ABB. All rights reserved...
  • Page 7: Main Features

    – via IEC61850-8-1 Edition 1 or Edition 2 Installation of bay units and central unit in one or – via IEC60870-5-103 several cubicles • Local HMI with comprehensive system information on – Distributed layout: every unit © Copyright 2019 ABB. All rights reserved...
  • Page 8: Mode Of Installation

    (see Figure • Check-zone protection The central processing unit is normally located in a • End-fault protection central cubicle or in a central relay room. • Definite time overcurrent protection © Copyright 2019 ABB. All rights reserved...
  • Page 9 19"racks (up to two bay units each rack), functionality can be packed into the same space. according to the size of the busbar system in one or more cubicles (see Figure 6). A centralized installation is © Copyright 2019 ABB. All rights reserved...
  • Page 10 Combined centralized and distributed installation philosophies. GUID-91E51CE6-A158-47B9-9197-922762650098 v1 Basically, the only difference between a distributed and a centralized scheme is the mounting location of the bay © Copyright 2019 ABB. All rights reserved...
  • Page 11: System Design

    Due to the modular and flexible attached to all the data such as currents, voltages, architecture of the software, integration of new units is binary inputs, events and diagnostic information easily achieved. acquired by a bay unit. © Copyright 2019 ABB. All rights reserved...
  • Page 12: Functionality

    Stabilized differential current measurement GUID-DF5D25BC-8988-48FD-B716-640BCB8809DD v1 The first measuring principle uses a stabilized differential current algorithm. The currents are evaluated individually for each of the phases and each section of a busbar (protection zone). © Copyright 2019 ABB. All rights reserved...
  • Page 13 Rest enables tripping only when a current above a certain minimum is flowing, or the voltage is below a certain IECEQUATION18124 V1 EN-US where value, respectively. stabilizing factor © Copyright 2019 ABB. All rights reserved...
  • Page 14 If the fault still persists at the end of the second time A definite time overcurrent back-up protection scheme delay, the breaker failure function uses the busbar can be integrated in each bay unit. (The operation of the © Copyright 2019 ABB. All rights reserved...
  • Page 15 GUID-35BC7349-3F0F-404C-866F-4D7B694B8478 v2 The events are recorded in each bay unit. A time stamp (SAS) is possible via the central unit. The interface with a resolution of 1 ms is attached to every binary © Copyright 2019 ABB. All rights reserved...
  • Page 16 The differential current is permanently supervised. Any • remain in operation differential current triggers a time-delayed alarm. In the event of a differential current alarm, it is possible to select the behavior of the busbar protection: © Copyright 2019 ABB. All rights reserved...
  • Page 17: Additional Features

    GUID-BEF56E90-7D57-4250-9B22-0272C77731E8 v1 After installation and commissioning, PCM600 offers and in the bay units comprises: easy access to the installed base of ABB substation • a graphical monochrome LCD with a resolution of automation products within the substation. The 320x240 pixels each for displaying system data and...
  • Page 18: Requirements

    IEC18000377 V1 EN-US • LC connector (for 62.5/50 μm optical fibers) Figure 11. Switching sequence of the auxiliary contacts that • rodent protected and longitudinally waterproof if in control the busbar replica cable ducts © Copyright 2019 ABB. All rights reserved...
  • Page 19 CT only conducts the current of  its own feeder. Should nevertheless CT saturation be    possible, it is important to check that the minimum fault current exceeds the setting for Kmin © Copyright 2019 ABB. All rights reserved...
  • Page 20: Reb500 Process Bus Configuration

    13 14 15 16  up to 60 Bay Units BU53 BU60        14000047-IEC18000347-1-en.vsd IEC18000347 V1 EN-US Figure 12. REB500 Process bus configurations up to 60 Bay Units © Copyright 2019 ABB. All rights reserved...
  • Page 21: Hardware Description

    265.9 mm 300 mm 254 mm 224 mm + 12 mm with ring lug connector 25.5 mm 13 mm 17000012-IEC18000378-1-en.vsdx IEC18000378 V1 EN-US Figure 13. Flush mounted Bay Unit into a panel cutout © Copyright 2019 ABB. All rights reserved...
  • Page 22 Two rack mounted IEDs 224 mm + 12 mm with ring lug 25.5 mm 482.6 mm (19”) 265.9 mm (6U) 13 mm 17000014-IEC18000380-1-en.vsdx IEC18000380 V1 EN-US Figure 15. Two rack mounted Bay Units side by side © Copyright 2019 ABB. All rights reserved...
  • Page 23 GUID-B5CF0FD7-F3D6-4AE0-BF0C-AE4F8F5E864D v1 Rack mounted IED 224 mm + 12 mm with ring lug connector 25.5 mm 482.6 mm (19") 265.9 mm (6U) 13 mm 17000015-IEC18000381-1-en.vsdx IEC18000381 V1 EN-US Figure 16. Rack mounted Central Unit © Copyright 2019 ABB. All rights reserved...
  • Page 24: Connection Diagrams

    X326 X326 X101 X101 X101 X307 X307 X307 X329 X329 X329 X324 X324 X324 X102 X102 X102 X304 X304 X304 X309 X309 X309 X410 X410 X410 Not used Option 17000016-IEC18000382-1-en.vsdx IEC18000382 V1 EN-US © Copyright 2019 ABB. All rights reserved...
  • Page 25 X1001 X1001 X347 X347 X1002 X1002 X1010 X1010 X334 X334 X339 X339 X1009 X1009 X304 X304 X349 X349 X1008 X1008 X415 X415 X450 X450 X1000 X1000 Not used Option 17000017-IEC18000383-1-en.vsdx IEC18000383 V1 EN-US © Copyright 2019 ABB. All rights reserved...
  • Page 26 Spare CR17 Spare CR18 Close Block CR19 GUID-AEDDEB1A-842A-4EE5-A472-137B1200278D V1 EN-US CR02-CR07 and CR11-CR13 Power output relays (see Remark: The signal configuration is an example only, the Table binary I/Os can be freely configured. © Copyright 2019 ABB. All rights reserved...
  • Page 27 TRIP CB L2_2 OC25 Spare TRIP2+ CR25 TRIP CB L3_2 OC26 Spare CR20-CR25 Precision tripping outputs OC27 Spare OC28 Spare Spare OC29 Spare OC30 Spare OC31 Spare OC32 Spare OC33 GUID-72E91BBA-CA2D-43E7-966D-D7A66B7161DB V1 EN-US © Copyright 2019 ABB. All rights reserved...
  • Page 28 Voltage input L2-E (Bus 2) ● Phase voltage L2 (Bus2 / 1ph L2-E) Voltage input L2-E (Bus 2)_0 ● Current/ voltage transformer fixed assignment ○ Only for busbar protection Io measurement (optional function) GUID-7A959BC3-4FF6-40EC-A2AB-06AD7027E868 V1 EN-US © Copyright 2019 ABB. All rights reserved...
  • Page 29 X4 (not used) IRIG-B X9 (not used) UART Power Supply: X410 48-125VDC 110-250VDC 100-240VAC DC / AC Supply 110-250VDC and 100-240VAC  Power supply version A 48-125VDC  Power supply version B GUID-6528A838-24E3-49B9-AF2B-16FE52F1A739 V1 EN-US © Copyright 2019 ABB. All rights reserved...
  • Page 30 Spare CR22 Spare CR23 Spare CR24 Spare CR25 Spare Spare CR26 Spare CR27 Spare CR28 GUID-3616C7B0-F3D2-4EFE-8954-4120F3A21754 V1 EN-US Remark: The signal configuration is an example only, the binary outputs can be freely configured. © Copyright 2019 ABB. All rights reserved...
  • Page 31 Spare OC12 Spare OC13 Spare OC14 Spare OC15 Spare OC16 Spare OC17 Spare OC18 Spare GUID-57EC4258-AA1C-45F1-AF58-C2ACBB578D76 V1 EN-US Remark: The signal configuration is an example only, the binary inputs can be freely configured. © Copyright 2019 ABB. All rights reserved...
  • Page 32 Power supply: X450 X415 (Option) Redundant power supply Main power supply 48-125VDC 48-125VDC 110-250VDC 110-250VDC 100-240VAC 100-240VAC 110-250VDC and 100-240VAC  Power supply version A 48-125VDC  Power supply version B GUID-3DFED090-AE7A-4B6C-A2B2-E5234EBEEAED V1 EN-US © Copyright 2019 ABB. All rights reserved...
  • Page 33: Technical Data

    0 to 420 V Thermal withstand: 450 V For 10 s 420 V Continuous Burden: At 110 V < 50 mVA At 220 V < 150 mVA **) All values for individual voltage inputs © Copyright 2019 ABB. All rights reserved...
  • Page 34 ≤0.5 A/≤0.1 A/≤0.04 A constant L/ R<40 ms, at U< 48/110/220 V DC Burden per CR: 258 mW CR2 - CR7, CR11 - CR13, CR20 - CR22 1) Internal fault relay – change over contact © Copyright 2019 ABB. All rights reserved...
  • Page 35 Connector Permitted path Distance attenuation 1300 nm MM 62.5/125 μm <8 dB 2 km MM 50/125 µm <6 dB 2 km glass fiber core Maximum allowed attenuation caused by connectors and cable together © Copyright 2019 ABB. All rights reserved...
  • Page 36 -40...+70ºC (<16h) Degradation in MTBF and HMI performance outside the temperature range of -25...+55ºC Relative humidity 5..95%, non-condensing Atmospheric pressure minimum 76 kPa Altitude up to 2000 m Transport and storage temperature range -40...+85ºC © Copyright 2019 ABB. All rights reserved...
  • Page 37 16 h at +70ºC IEC60068-2-2/ANSI C37.90-2005 (chapter 4) storage 96 h at +85ºC Damp heat tests steady state 240 h at +40ºC IEC60068-2-78 humidity 93% cyclic 6 cycles at +25 to +55ºC IEC60068-2-30 humidity 93...95% © Copyright 2019 ABB. All rights reserved...
  • Page 38 2 kV line-to-earth, 1 kV line-to-line level 3/2 Power frequency (50 Hz) magnetic IEC61000-4-8, level 5 field 1000 A/m Continuous 100 A/m Power frequency immunity test IEC60255-26 IEC61000-4-16 Common mode 300 V rms Differential mode 150 V rms © Copyright 2019 ABB. All rights reserved...
  • Page 39 1 kV, unipolar impulses, waveform 1.2/50 μs, source energy 0.5 J, communication Insulation resistance measurements IEC60255-27 ANSI C37.90-2005 Isolation resistance >100 MΩ, 500 V DC Protective bonding resistance IEC60255-27 Resistance <0.1 Ω (60 s) © Copyright 2019 ABB. All rights reserved...
  • Page 40 Diff kmin for f = 50, 60 Hz For details about pickup accuracy, see REB500 Application Note - Verification of pickup values available in the REB500 Product CD , Section Application Notes . © Copyright 2019 ABB. All rights reserved...
  • Page 41 For feeders with single phase tripping and autoreclosure, the time setting for the breaker pole discrepancy protection must be greater than the reclosure time. The discrepancy factor is the maximum permissible difference between the amplitudes of two phases. © Copyright 2019 ABB. All rights reserved...
  • Page 42 The check zone is used as an additional release criterion for busbar protection and operates zone-independent. REB500 Application Note - Verification of pickup values available in the REB500 Product CD , Section Application Notes . For details about pickup accuracy, see © Copyright 2019 ABB. All rights reserved...
  • Page 43 Operation in conjunction with distance, overcurrent and synchrocheck functions and also with external protection and synchrocheck relays Logic for first and second main protections, duplex and master/follower schemes Up to four fast or slow reclosure shots Detection of evolving faults Four independent parameter sets © Copyright 2019 ABB. All rights reserved...
  • Page 44 Number of disturbance records = total recording time / set recording period (max.40) Buffer overflow behavior is first in first out. Independent settings for pre-fault and post-fault period (min. setting 200 ms). Format: COMTRADE 99 © Copyright 2019 ABB. All rights reserved...
  • Page 45 0...255 (CAA) ADSU CAA per bay unit freely selectable Hardware IED GUID-FA7506E7-6A34-4DB9-93B8-41130E9F7BC0 v1 Table 40. Degree of protection of rack-mounted IED Description Value Front side IP 40 Rear side, connection terminals IP 20 © Copyright 2019 ABB. All rights reserved...
  • Page 46: Ordering For Customized Ied

    12. Ordering for customized IED hardware selections. Guidelines GUID-432D4232-0B87-40F0-A98E-94827BC77E71 v2 Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain © Copyright 2019 ABB. All rights reserved...
  • Page 47 Bay Unit Order Code rules Software option multiple selection is possible Connection type and Power Supply selection must be combined Analogue input and Analogue connection selection must be combined © Copyright 2019 ABB. All rights reserved...
  • Page 48 PSM03: 100VAC-240VAC, 110VDC-250VDC, 9BO PSM02: 48VDC-125 VDC, 9BO Power supply (redundant) No redundant power supply PSM03: 100VAC-240VAC, 110VDC-250VDC PSM02: 48VDC-125 VDC Human Machine Interface LHMI: OL5100, IEC 6U ¾ 19”, Basic IEC19000473 V1 EN-US © Copyright 2019 ABB. All rights reserved...
  • Page 49 No board in this slot BIO01: 9BI, 9BO Communication and processing module CPM: 12BI, IRIG-B, RS485, Ethernet, LC optical, ST connector CPM: IRIG-B, RS485, 3 Ethernet LC optical, ST serial, ST PPS slave IEC19000474 V1 EN-US © Copyright 2019 ABB. All rights reserved...
  • Page 50 Flush mounting kit 6U 1/2x19" case Wall mounting bracket Connection type for Power supply, I/O and Communication modules Compression terminals Ringlug terminals Power Supply PSM03: 100VAC-240VAC, 110VDC-250VDC, 9BO PSM02: 48VDC-125 VDC, 9BO IEC19000475 V1 EN-US © Copyright 2019 ABB. All rights reserved...
  • Page 51 CPM: 10BI, IRIG-B, RS485, Ethernet, LC optical, ST connector IEC19000476 V1 EN-US * PIO01 only in with analogue input module TRM01: 4I, 1/5 A + 1I, 0.1/0.5 A +5U, 100/220 V (Options SA3/RA3) © Copyright 2019 ABB. All rights reserved...
  • Page 52 24 BU 22 +6 = 28 n BUs Switch data 110/250 V DC / 110/230 V AC no redundant power supply module IEC19000478 V1 EN-US For details about REB500 process bus/switch configuration, see Section © Copyright 2019 ABB. All rights reserved...
  • Page 53: Manuals

    Technical manual for bay protection functions 1MRK 505 406-UEN Cyber security deployment guideline 1MRK 511 453-UEN Communication protocol manual IEC61850 1MRK 511 450-UEN Communication protocol manual IEC60870-5-103 1MRK 511 451-UEN Getting started guide 1MRK 505 404-UEN © Copyright 2019 ABB. All rights reserved...
  • Page 55 ABB AB Grid Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 Scan this QR code to visit our website www.abb.com/protection-control © Copyright 2019 ABB. All rights reserved.

Table of Contents