6 Parameters

6.1 Parameter Group O-##

O-01 Control Site
Option:
[0] *
Digital and ctrl.word
[1]
Digital only
[2]
Controlword only
O-02 Control Word Source
Select the source of the control word: one of two serial interfaces or four installed options. During initial power-up, the frequency converter automatically sets
this parameter to Option A [3] if it detects a valid network option module installed in slot A. If the option is removed, the frequency converter detects a change
in the configuration, sets par. O-02 Control Word Source back to default setting Drive RS485, and the frequency converter then trips. If an option is installed
after initial power-up, the setting of par. O-02 Control Word Source will not change but the frequency converter will trip and display: Alarm 67 Option
Changed.
This parameter cannot be adjusted while the motor is running.
Option:
[0]
None
[1]
Drive RS485
[2]
Drive USB
[3] *
Option A
[4]
Option B
[5]
Option C0
[6]
Option C1
O-03 Control Word Timeout Time
Range:
1.0 s*
[0.1 - 18000.0 s]
O-04 Control Word Timeout Function
Select the time-out function. The time-out function activates when the control word fails to be updated within the time period specified in par. O-03 Control
Word Timeout Time.
Option:
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[7]
Select setup 1
Function:
The setting in this parameter overrides the settings in par. O-50 Coasting Select to par. O-56 Preset Ref-
erence Select.
Control by using both digital input and control word.
Control by using digital inputs only.
Control by using control word only.
Function:
Function:
Enter the maximum time expected to pass between the reception of two consecutive messages. If this
time is exceeded, it indicates that the serial communication has stopped. The function selected in
par. O-04 Control Word Timeout Function will then be carried out. The time-out counter is triggered by a
valid control word.
Function:
Resumes control via serial bus (Network or standard) using the most recent control word.
Freezes output frequency until communication resumes.
Stops with auto restart when communication resumes.
Runs the motor at JOG frequency until communication resumes.
Runs the motor at maximum frequency until communication resumes.
Stops the motor, then resets the frequency converter in order to restart: via the network, via the reset
button on the Keypad or via a digital input.
Changes the set-up upon reestablishment of communication following a control word time-out. If com-
munication resumes causing the time-out situation to disappear, par. O-05 End-of-Timeout Function de-
OPCEIP EtherNet/IP