Ethernet/Ip Connections; Class 1 Connection - GE AF-650 GP Operating Instructions Manual

Opceip ethernet/ip
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

NB!
Use of 32-bit process data.
For configuration of a 2-word (32-bit) parameter read/write, use 2 consecutive arrays in par. EN-21 and EN-22, like [2]+[3], [4]+[5], [6]+[7] etc. Read/write of 2-
word values in arrays like: [3]+[4], [5]+[6], [7]+[8] are not possible.

5.1.2 EtherNet/IP Connections

The OPCEIP option supports the CIP connections described in the following sections:

5.1.3 Class 1 connection

5
I/O connection using TCP transport. Maximum one Class 1 connection is supported by the EtherNet/IP option, but several listen only connection can be established
if multicast is selected as Transport type. This type of connection is used for cyclic I/O and Change-Of-State connections. The connection is established with a
Forward Open command, containing the following information:
Transport Type:
Specified for both directions:
-
Originator-to-Target / Target-to-Originator.
-
Point to Point
-
Multicast (Target-to-Originator only)
Data Size:
Specified (in bytes) for both directions: Originator -> Target / Target -> Originator.
The data-size depends on the assembly-instance chosen in: Destination.
Instances (decimal)
Originator →Target
20, 21, 100
101
103
Packet Rate:
Specified (in milliseconds) for both directions: Originator -> Target / Target -> Originator.
Minimum packet rate supported: 1 ms
Production Inhibit Timeout:
Specifies (in milliseconds) the timeout-time for both directions.
Trigger:
Selects the transport trigger type:
-
Cyclic (Data is transmitted cyclically as polled I/O)
-
Change Of State (Data is transmitted on Change of State only. COS-filters are set-up in par. EN-38 COS Filters)
Connection Points
Specified for both directions: Originator -> Target / Target -> Originator.
Profile
(par. O-10 Control Word Profile)
ODVA
Drive
22
Target →Originator
70, 71, 150
151
153
Direction
Originator →Target
Target →Originator
Originator →Target
Target →Originator
OPCEIP EtherNet/IP
Data Size
4 bytes
8 bytes
20 bytes
Connection Points
(decimal)
20, 21
70, 71
100, 101, 103
150, 151, 153

Advertisement

Table of Contents
loading

This manual is also suitable for:

Af-600 fp

Table of Contents