5.3 ODVA Control Profile

5.3.1 Control Word under Instances 20/70 and 21/71

Set par. O-10 Control Word Profile to ODVA.
The control word in Instances 20 and 21 is defined as follows:
5
NB!
Bits 00 and 02 in Instance 20 are identical with bits 00 and 02 in the more extensive Instance 21.
Bit
00
01
02
03
04
05
06
07-15
Explanation of the Bits:
Bit 0, Run Fwd:
Bit 0 = "0" means that the drive has a stop command. Bit 0 = "1" leads to a start command and the drive will start to run the motor clockwise.
Bit 1, Run Rev:
Bit 1 = "0" leads to a stop of the motor. Bit 1 = "1" leads to a start of the motor.
Bit 2, Fault Reset:
Bit 2 = "0" means that there is no trip reset. Bit 2 = "1" means that a trip is reset.
Bit 3, No function:
Bit 3 has no function.
Bit 4, No function:
Bit 4 has no function.
Bit 5, Net Control:
Bit 5 = "0" means that the drive is controlled from the standard inputs. Bit 5 = "1" means that EIP controls the drive.
NB!
Please note that changes will affect parameters O-50 to O-56.
28
Instance 20
Bit = 0
Stop
Run
-
-
No function
Fault reset
-
-
-
-
-
-
-
-
-
-
Bit =1
Bit = 0
Fwd Stop
Stop
No function
-
-
-
-
-
OPCEIP EtherNet/IP
Instance 21
Bit =1
Run Fwd
Run Rev
Fault reset
-
-
Net Ctrl
Net Ref
-