4.2.6

System Configuration for connecting to CS1H, CS1G, or CS1D

When connecting to a PLC or a serial communication module
Serial
CS1H
communication
CS1G
module
CS1D
/RS-422 converter
PLC
Serial
communication
Model
*1
name
module
/RS-422A converter
-
CS1W-SCU21
CS1W-SCU21-V1
CS1H
CS1G
CS1D
CJ1W-CIF11
*1
Product manufactured by OMRON Corporation. For details on the product, contact OMRON Corporation.
*2
Connect it to the RS-232 interface (built into GOT). It cannot be mounted on GT1655 and GT155 .
4 - 14
4. CONNECTION TO OMRON PLC
4.2 Serial Connection
Connection cable
Communication
Cable model
Type
Connection diagram number
GT09-C30R20101-9P(3m)
RS232 connection diagram 1)
RS-232
RS232 connection diagram 4)
GT09-C30R20101-9P(3m)
RS232 connection diagram 1)
RS-232
RS232 connection diagram 4)
RS422 connection diagram 4)
GT09-C30R40103-5T(3m)
GT09-C100R40103-5T(10m)
GT09-C200R40103-5T(20m)
RS-422
GT09-C300R40103-5T(30m)
RS422 connection diagram 8)
RS422 connection diagram 12)
Connection cable
Max.
distance
or
15m
15m
or
15m
15m
50m
50m
or
50m
GOT
GOT
Option device
Model
-
(Built into GOT)
GT15-RS2-9P
-
(Built into GOT)
-
(Built into GOT)
GT15-RS2-9P
-
(Built into GOT)
-
(Built into GOT)
GT16-C02R4-
9S
(0.2m)
GT15-RS2T4-
*2
9P
GT15-RS4-9S
-
(Built into GOT)
-
(Built into GOT)
Communication driver
OMRON SYSMAC
Number of
connectable
equipment
1 GOT for 1 PLC
1 GOT for 1
serial
communication
module
1 GOT for 1 RS-
422A converter

Advertisement