8.4

Buffer memory details

The following indicates the buffer memory details of the PROFIBUS profiles.
 PKW
Name
PNU
0 to 10
SPM
11
PKE
AK
12 to 15
PP
0 to 7
IND
IND
8 to 15
66
PPO TYPE NON-SUPPORT SPECIFICATION
Bit
PNU number (Together, the PNU and the IND define which data word is being accessed.)
Not used (0 is set)
[Command request]
0: No task
1: Parameter value is requested (read request)
2: Parameter value (word) is changed (write request)
Others: Not supported
[Command response]
0: No response (Busy status)
1: Inverter can accept data (Ready status)
7: Command execution error (error number is stored into PWE) (Refer to the next page)
8: No operation change rights (error number is stored into PWE) (Refer to the next page)
Others: Not used
Page Index:
• If IND = 1 (system environment variables (sev) area), the PP values specify different blocks of sev's:
PP = 0: sev_I, block I
PP = 1: sev_II, block II (alarm history)
PP = 2: sev_III, block III
(For details, refer to
page
• If IND is other than 1, set PP to 0.
Parameter Index:
Specifies the area from which Parameter Number (PNU) is being accessed.
(For details, refer to
page
IND = 0: real-time monitor area
IND = 1: system environment variable (sev) area (3 blocks)
IND = 2: normal parameter area
IND = 3: Pr.900 to calibration parameter (frequency) area
IND = 4: Pr.900 to calibration parameter (%) area
Definition
71.)
70.)