Inverter Reset - Mitsubishi Electric 800 Series Instruction Manual

Plug-in option, profibus-dp communication function
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

4.4

Inverter reset

 Operation conditions of inverter reset
Which resetting method is allowed or not allowed in each operation mode is described below.
Inverter reset (Refer to
Reset from the
Error reset (STW (bit 7)) at inverter fault
network
(Refer to
Turn on the inverter RES signal (terminal RES)
Switch off inverter power
Inverter reset
Reset on the
operation panel
Reset at inverter fault
*1
Inverter reset can be made any time.
*2
Reset can be made only when the protective function of the inverter is activated. (Available with PPO type 1 to 5 only)
NOTE
• When a communication line error has occurred, reset cannot be made from the network.
• The inverter is set to the External operation mode if it has been reset in Network operation mode in the initial status. To
resume the network operation, the inverter must be switched to the Network operation mode again. Set a value other than
"0" in Pr.340 to start in the Network operation mode. (Refer to
• Communication continues during inverter reset. (The inverter cannot be controlled for about 1 second after release of a
reset command.)
Resetting method
*1
page
53.)
*2
page
47.)
Network
operation
Allowed
Pr.349 = 0
Allowed
Pr.349 = 1
Allowed
Allowed
Allowed
Allowed
page
24.)
Operation mode
External
PU operation
operation
Disallowed
Disallowed
Allowed
Allowed
Disallowed
Disallowed
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
INVERTER SETTING
4
33