Communication System Manual
The FBs SEND and REC are assigned to data blocks when they are called. DB80 contains the
message headers for message group 0 and DB81 contains the message headers for message group 1.
These blocks are structured such that the basic data word (DW no.) can be calculated as follows for a
message number (T-Nr.):
DW no. = 2 x T-Nr.
The parameter identifier is stored in the basic data word. The following data word contains the
parameter subindex.
The data to be sent and the data to be received (to/from 3WN6) are also stored in data blocks (in the
example: DB230 and DB220).
Block call structure of example:
OB1
Contents and function of data blocks:
DB80
DB81
DB210 (DBG0)
DB220 (DBG1)
DB230 (DBSZ)
DB240 (DBAT)
64
FB10
DB header, assignment of parameter identifier for message group 0
DB header, assignment of parameter identifier for message group 1
Storage locations for read circuit-breaker data
Storage locations for read operational data of circuit-breaker (actual values!)
Storage locations for operational data to be sent to the circuit-breaker
Storage locations for T-Nr. enable, priority assignment and request coordination
- old values which have already been written to the circuit-breaker
© Copyright Siemens AG 1998. All rights reserved.
3WN6 Circuit-Breakers
FB81
DB80
DB81
FB82
DB210
FB100
DB220
FB101
DB230
FB102
DB240
Version 1.0 (02/98)