Communication System Manual
The interface module has been tested in accordance with the tests, standards and specifications outlined in
the following table.
Table 15 Tests, standards and specifications
No.
1
Vibration test
2
Shock test
3
Drop test
4
Bending and draw-out test
5
Climatic test:
6
Pollutant concentration
7
ESD
8
Electromagnetic fields
9
Burst
10
Emitted interference
11
Approvals
12
Standards, specifications
13
Siemens standards
104
Parameter
• 5 Hz ≤ f ≤ 26 Hz, amplitude =
0.75 mm
• 26 Hz ≤ f ≤ 500 Hz, acceleration =
20 m/s
à
à
• Shock form = half sinusoidal
• Acceleration = 15 g (150 m/s
• Duration of shock = 11 ms
à
• Screw size: M3
• Wire cross-section: 0.75/1.5/2.5 mm
• Wire type
• 0 °C/16 h
- Cold
• 60 °C/16 h
- Dry heat
• -25 °C ... 55 °C, 1 °C/min, 2 cycles
- Change of temp.
• 55 °C, 90 ... 95 %, 12+12h, 2 cycles
- Damp heat
• SO2 < 0.5 ppm; rel. humidity < 60 %
• H2S < 0.1 ppm; rel. humidity < 60 %
2 kV/5 kHz supply voltage
2 kV/5 kHz data cables
• UL
• CSA
• CE mark
• PROFIBUS certification
• DIN 40050; IEC 529
• VDE 0106, protection class 3
• VDE 0160, where applicable
• VDE 0110 - insulator group IIIa, IIIb
• IEC 68
• IEC 721-3-1/-3
• IEC 1131-2
• IEC 1000-4-2/-3/ -4/ -5/ -6
• EN 55011, DIN VDE 0875-11
• EN 50022
• EN 61131-2
• UL 508
• CSA 22.2-14
• SN 18013
• SN 18012
• SN 36350
• SN 31205
© Copyright Siemens AG 1998. All rights reserved.
Data
2
Frequency sweep: 1 octave/min
10 freq. sweeps each in x, y, z
2
3 shocks in +/- direction in x, y, z
1m high
--> tightening torque: 0.5 ... 0.8 Nm
AWG: 18/16/14
: rigid, flexible
8 kV discharge in air
6 kV contact discharge
10 V/m
Limit class A
- pollution severity 3
3WN1, 3WS1 Circuit-Breakers
Description
ð
SN 31205
(IEC 68-2-6-Fc sinusoidal)
(= utilization category: 3M6/1M4)
ð
SN 31205
(IEC 68-2-27-Ea)
(= utilization category: 3M6/1M4)
)
ð
SN 18013
ð
IEC 947-1 (screw connections)
2
ð
SN 31205
(IEC 68-2- 1-Ad,
IEC 68-2- 2-Bd,
IEC 68-2-14-Nb,
IEC 68-2-30-Db)
(= utilization category: 3K6/1K6)
ð
SN 31205
(IEC 68-2-60)
(= utilization category: 3C3/1C2)
ð
No condensation
IEC 1000-4-2
Severity 3
IEC 1000-4-3
Severity 3
IEC 1000-4-4
Severity 3
EN 55011
ð
Underwriters Laboratories
ð
Canadian Standards
Association
ð
Certificate of conformity from
ð
PROFIBUS user organization
ð
IP degrees of protection
ð
Shock protection, protective
separation
ð
Power installations
ð
Insulation coordination
ð
Env. conditions: Meas. methods
ð
Env. conditions: Definitions
ð
PLC interface standard
ð
EMC requirements
ð
EMC emissions
ð
Standard DIN rail
ð
PLC I/O modules
ð
UL for indust. control systems
ð
CSA for industrial equipment
ð
Packaging and drop test
ð
Labeling of packaged items
ð
Recycling guidelines
ð
Environmental conditions