Analog modules
6.8 Analog input module SM 331; AI 2 x 12 Bit; (6ES7331-7KB02-0AB0)
6.8.3
Programmable parameters
Introduction
For general information on programming analog modules, refer to the chapter Programming
analog modules (Page 294).
Parameters
Table 6- 22
Overview of the parameters of SM 331; AI 2 x 12 Bit
Parameters
Enable
•
Diagnostics interrupt
•
Process interrupt when limit
exceeded
Process interrupt trigger
•
High limit
•
Low limit
Diagnostics
•
Group diagnostics
•
with line continuity check
Measurement
•
Measurement type
•
Measuring range
•
Noise suppression
See also
Diagnostics messages of analog input modules (Page 296)
378
Range of values
yes/no
yes/no
32511 to -32512
from - 32512 to 32511
yes/no
yes/no
disabled
Voltage V
4DMU current (4-wire transducer)
2DMU current (2-wire transducer)
R-4L resistance (4-wire connection)
RTD-4L thermoresistor
(linear, 4-wire connection)
TC-I thermocouple
(internal comparison)
TC-E thermocouple
(external comparison)
TC-IL thermocouple
(internal comparison)
TC-EL thermocouple
(linear, external comparison)
Refer to the chapter Measuring methods
and ranges (Page 376) for the adjustable
measuring ranges of the input channels
400 Hz; 60 Hz; 50 Hz; 10 Hz
Default
Parameter
type
no
dynamic
no
-
dynamic
no
static
no
V
dynamic
± 10 V
50 Hz
Manual, 06/2017, A5E00105505-AJ
Scope
Module
Channel
Channel
group
Channel or
channel
group
S7-300 Module data