3.32 Digital output module SM 322; DO 8 x AC 120/230 V/2 A ISOL (6ES7322-5FF00-0AB0)
Configuration in RUN
Special considerations must be given if you use the Configuration in RUN function.
SF LED is lit:
Status before re-configuration diagnostics on, SF LEDs lit among others (on CPU, IM or
module), although diagnostics are no longer pending and the module is operating correctly.
Solution:
● Only change the configuration when no diagnostics are pending for the module or
● Pulling and plugging the module.
3.32.1

Parameters of SM 322; DO 8 x AC 120/230 V/2 A ISOL

Parameters of SM 322; DO 8 x AC 120/230 V/2 A ISOL
The table below lists the configurable parameters of SM 322; DO 8 x AC120/230 V/2 A
ISOL, including defaults.
The defaults apply if you have not set any parameters in
Table 3- 32
Parameters of SM 322; DO 8 x AC 120/230 V/2 A ISOL
Parameters
Enable
Diagnostic interrupts
Reaction to CPU STOP
Set substitute value "1"
Programming
For detailed information on parameters of the digital output module, refer to the appendix
Settings for the digital output modules (Page 528).
See also
Programming digital modules (Page 58)
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
Range of values
yes/no
Set substitute value (SSV)
Hold last value (HLV)
yes/no
STEP 7
Defaults
Parameter type
no
dynamic
SSV
dynamic
no
dynamic
Digital modules
.
Scope
Module
Channel
Channel
195