Mitsubishi Electric 800 Series Instruction Manual page 49

Communication
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Item
Data
H00
H01
*1
Reply code 1
H03
H00
H01
Reply code 2
H02
H03
*1
The contents of the reply code 1 are changed when torque commands are given or the torque is limited. (when Pr.544 = "14 or 18").
The upper 4 bits of the reply code 1 are used as the reply code to the torque command / torque limit, and the lower 4 bits are used as the reply
code to the frequency command.
Bit15
Reply code2
Example) When the torque command is out of the setting range, the data is H0030.
Bit15
0
0
0
0
 Instruction code
Set instruction codes using the remote register (RWw). (Refer to
The definition read by the instruction code is stored in the remote register (RWr). (Refer to
Item
Operation mode
Output frequency /
rotations per minute
(machine speed)
Output current
Monitor
Output voltage
Special monitor
Special monitor
selection No.
48
2. Ethernet Communication
2.6 CC-Link IE Field Network Basic
Item
Normal
Write mode fault
Frequency command (torque
command / torque limit)
setting range error
Normal
Write mode fault
Parameter selection fault
Setting range fault
Reply code to
the torque command /
torque limit
0
0
0
0
0
0
Reply code to
the torque command
Read/
Instruction
write
code
Read
H7B
Write
HFB
Read
H6F
*1*2
Read
H70
Read
H71
*2
Read
H72
Read
H73
*3
Write
HF3
Fault record
No fault (Instruction codes are executed
without any fault.)
Parameter write is attempted when the
inverter is not in the stop status in the
Network operation mode.
The value outside the range is set.
No fault (Instruction codes are executed
without any fault.)
Parameter write is attempted when the
inverter is not in the stop status in the
Network operation mode.
Unregistered code is set.
Set data exceeds the permissible range.
Bit0
Reply code to
the frequency
command
Reply code1
Bit0
1
1
0
0
0
0
page
45.)
H0000: Network operation
H0001: External operation, External JOG operation
H0002: PU operation, External/PU combined operation 1 or 2, PUJOG operation
H0000: Network operation
H0001: External operation
H0002: PU operation (when Pr.79 = "6")
H0000 to HFFFF:
Output frequency in 0.01 Hz increments (The display can be changed to the
rotations per minute (machine speed) using Pr.37 and Pr.53. (Refer to the FR-
E800 Instruction Manual (Function).)
H0000 to HFFFF:
Output current (hexadecimal) in 0.01/0.1 A increments
H0000 to HFFFF:
Output voltage (hexadecimal) in 0.1 V increments
H0000 to HFFFF: Monitor data selected in the instruction code HF3
H01 to HFF: Monitor selection data
Refer to the monitor code description on
Remarks
Reply code to RWr2 when
Pr.544 ≠ "0".
page
47.)
Data description
*4
page
50.