SINAMICS S120 at Technology CPU Entry ID: 21767896
No.
5.
6.
7.
To ensure that the recovered data are loaded back to the SINAMICS S120
drive system during the next reboot, these data finally have to be copied
from RAM to ROM via the context menu of SINAMICS S120 from where
they are loaded during the next startup of SINAMICS S120.
V1.0
Instruction
Edition 10/28/05
Requirements
Data Backup of SINAMICS S120
Note
In the expert list, select parameter
p976.
Click in the input box for the
parameter value to call the list for
the input options.
Select the desired backup file 10,
11 or 12.
Acknowledge your selection with
the enter key. The data backup is
started and the text Start loading
parameters saved with p977=xx is
displayed in the parameter field.
Loading the data is completed as
soon as the text Not active (0) is
displayed in the in the parameter
field of parameter p976 and the
text Ready (0) appears in the
parameter field of parameter p9 .