SINAMICS S120 at Technology CPU Entry ID: 21767896
To permanently back up changes in the parameter data or in the BICO
interconnection in SINAMICS S120, it is required to additionally copy the
data from the RAM to the compact flash card from where they are loaded
back to the CU320 control unit during the next startup of the drive system.
The data are backed up from the RAM of the control unit to the compact
flash card using the Copy RAM to ROM command from the context menu
of SINAMICS S120 in S7T Config.
Figure 4-3 Backing up data on compact flash card – Copy RAM to ROM
In the overview tree of S7T Config, several context menus are available
Note
for the data download. However, two different downloads exist: Global
download to SINAMICS S120 and partial download to the respective
component of SINAMICS S120.
For the data download to SINAMICS S120, please consider the
respective indicated context menu to ensure that the required volume of
data is transferred to the drive system.
V1.0
Data Backup of SINAMICS S120
Edition 10/28/05
Requirements
24/58