Advertisement

Cabinet Modules
5.6 Chassis format Motor Modules
Configuration
Motor Modules contain the following components as standard:
● Retaining device for the DC busbar, including the interface to the DC connections of the
● Connection busbar for motor cables for Motor Modules with frame sizes FX and GX; for
● Cable propping bar for the electric power cables
● DRIVE-CLiQ interface (3 DRIVE-CLiQ sockets), without Control Unit
● 6-pole auxiliary voltage supply, including auxiliary power module and cables for looping
● PE busbar (60 x 10 mm), including jumper for looping through to the next Cabinet
● EMC-compliant design thanks to additional shielding measures and appropriate laying of
Note
Additional information
The configuration examples of the individual Motor Modules are used to illustrate the
positioning of the factory-fitted components. They show the maximum possible configuration
of the modules, which contain all options that can be ordered.
Refer to the layout diagrams (AO) on the customer DVD for the precise order-specific
location of the components.
214
Motor Module (the necessary DC busbar must be provided separately as option M80 to
M87).
Motor Modules with frame sizes HX and JX, the motor cables are connected directly to
the device.
through to the next Cabinet Module.
Module.
cables.
Cabinet Modules
Manual, 03/2013, A5E03263538A