Running
Parameter
Parallel
Communication
Configuration
Modbus Config
HALL Reverse
Config
Basic Information
3.
Figure 5-12 Time
Figure 5-13 IP Address
Issue 07 (2019-12-30)
Description
This parameter needs to be set when multiple iBOXs are connected
in parallel and does not need to be set when there is only one
iBOX. Set Whether the iBOX communicates directly with the
NetEco to Yes, and set Number of iBOX configured under each
UPS. Configure IP addresses for multiple iBOXs.
Set ModbusTCP encryption and ModbusTCP authentication,
which are consistent with Connection Mode on the NetEco.
If the Hall effect sensor is reversely installed, you can set reverse
connection to correct it.
If a BCB box is configured, set BCB configuration to Done and
Batt. abnormal BCB trip to Enable.
On the System Settings page, set Time, IP Address, Battery Curve and Parallel Net
Join Config.
Copyright © Huawei Technologies Co., Ltd.
5 System Commissioning