5.5 Installing Cables

This section describes the cable routing specifications, connection preparations, and cable
connection methods. The figures are for reference only.

5.5.1 Cable Routing Rules

Binding Cables
Table 5-3 Cable binding rules
No.
1
2
3
Issue 01 (2016-03-04)
The figures are for reference only. The actual product appearance prevails.
Cable Binding Rule
Power cables and signal cables are bound separately with a distance above
150 mm.
Both ends of a cable are labeled. Labels are clean and correct, and provide
concise and understandable description.
Cable ties are neatly cut without sharp burs, evenly distributed, bound to a
proper strength, and fastened towards the same direction if possible, as