PDU8000 UPS Power Distribution Cabinet
User Manual
Figure 5-3 Leveling the feet
Step 2 Align the PDC mounting holes with the expansion bolt holes.
Step 3 Level the cabinet using a level and an adjustable wrench, as shown in
Issue 01 (2016-03-04)
Wrench an anchor bolt clockwise to elevate a cabinet foot, or wrench an anchor bolt anticlockwise to
lower it. The cabinet feet can be adjusted within a range of 0–8 mm.
To prevent cabinet tilting, adjust all the feet at the four corners instead of one foot.
Do not remove anchor bolts. Otherwise, you need to rework them for use.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Installation Guide
Figure
5-4.
39