Siemens DMS8000 Application & Planning page 32

Hide thumbs Also See for DMS8000:
Table of Contents

Advertisement

Automation level configurations
See MM8000 MP4.81 Release Notes (Doc. # A6V10062509)
32
Building Technologies
CPS Fire Safety
Subsystems that can be connected in this way
Type
Name
Fire panel
CS11 AlgoRex
Fire panel
CZ10
Intrusion panel
CS440
Intrusion panel
CS4
Intrusion panel
CZ12
Gas panel
CC60
Digital PLC unit
MF/MM7033
Système de
STT11
Télécommande et
Télésignalisation
Network devices required
Type
Gateway for Cerloop
Gateway for CS11
Gateway for STT11
Additional components required for the various management station types
Type
Foreign station
MM8000
Limits and restrictions
Type
Version
MM8000
MP4.81
MK8000
Note: Up to four data evaluation devices (MM8000/MK8000/MF7033) may be con-
nected to the Cerloop.
049_DMS_DMS8000_Application_Specification_Planning_MP4.81_A6V10063710_a_en.doc
Name
MK7022
CK1142/43
SK11
Additional
components
OPC client head end
OPC Server
ISO1745 Driver
ISO1745 Driver
Restrictions
With stand-alone/server stations, up to three serial
connections to ISO1745 driver (three MK7022).
More lines can be supported via FEP stations
(max 8 lines per FEP).
Supported by
MM8000
MP4.81
X
X
X
X
X
X
X
X
Version
Name
Version
Any OPC DA/UA
OPC DA2.0x
compliant client
OPC UA 1.02
MK8000
MP4.81
NS8010
NS8010
MP4.81
MK8000
MP4.81
X
X
X
X
X
X
X
X
09.2016

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nk8000Mm8000Mk8000

Table of Contents