Siemens SINAMICS S120 Equipment Manual page 392

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Accessories
7.2 DC link rectifier adapter
CAUTION
To ensure safe electrical separation, the 24 V supply cables and those for the DC link
connection cables must be physically separated (> 100 mm), or the 24 V cables must be
doubly insulated (e.g. light plastic-sheathed cable).
The DC link connection cables must be routed in such a way as to ensure that they are
ground-fault and short-circuit proof in accordance with DIN/VDE 0100 or suitable fuse
protection must be provided.
CAUTION
The total length of the DC link (including the connection cables) must not exceed 10 m.