Line Modules Booksize
3.5 Smart Line Modules (5 kW und 10 kW) with internal air cooling
Internal air cooling
Rated power
Circuit-breaker type designation
(status 07/2007and later)
Rated current
Short-circuit current rating SCCR at 400 V
UL safety fuse type AJT Class J
Rated current
Short-circuit current rating SCCR at 600 V
Cooling method (internal air cooling)
Sound pressure level
Cooling air requirement
Rated voltage for rated data 380 V 3 AC
Weight
1 The specified values apply to 380 V
2 For an overview, see the power loss tables in Cabinet Design chapter.
Rated duty cycles of Smart Line Modules
Figure 3-58
230
6SL3130–
kW
3RV1042-
A
kA
AC
A
kA
AC
dB(A)
m
/h
3
kg
Rated duty cycles of Smart Line Modules
6AE15–0AAx
5
4BA10
14 ... 20
100
AJT16
16
200
Internal fan
<60
29.6
4.7
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
6AE21–0AAx
10
4FA10
28 ... 40
100
AJT35
35
200
Internal fan
<60
29.6
4.8