Mounting; Technical Data - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

5.4.5

Mounting

See the instructions for installing other DC link components (e.g. Braking Module, Capacitor
Module).
Arrangement of the Voltage Clamping Module:
The Voltage Clamping Module should ideally be placed directly next to the Line Module.
● For Line Modules up to and including 36 kW, it should be placed to the right of the Line
● For Active Line Modules as of 55 kW, it should be placed to the left of the Line Module
● If the Voltage Clamping Module is to be installed in an existing drive line-up, it can also
5.4.6

Technical data

Table 5-10
Technical data
Voltage Clamping Module
Electronics power supply
DC link voltage
DC link busbar current carrying
capacity
24 V busbar
current carrying capacity
Power loss
1
Weight
1 For an overview, see the power loss tables in Chapter Cabinet design
SINAMICS S120 Booksize Power Units
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
Module.
due to the current-carrying capacity of the DC link busbars.
be placed at the end.
V
DC
V
DC
A
A
W
kg
Booksize DC Link Components
5.4 Voltage Clamping Module
24 (20.4 - 28.8)
510 - 720
100
20
50
3.1
361