Starting conditions
To start the control, the following conditions must be satisfied.
The necessary conditions must be incorporated in the program so that the axis is not started when the conditions are not
satisfied.
Starting conditions of the axis are mainly controlled by the state transition and the signal state of the axis and axes group.
Starting conditions for motion function blocks of the axis
■State transition
Name
Axis state
■Signal state
Signal name
I/O signal
PLC READY [Y0]
Ready [X0]
Synchronization flag [X1]
Use in axes group
Homing request
External signal
Forced stop cancelling
Upper limit signal status
Lower limit signal status
Stop status
Starting conditions for motion function blocks of the axes group
■State transition
Name
Axis state
Axes group state
■Signal state
Signal name
I/O signal
PLC READY [Y0]
Ready [X0]
Synchronization flag [X1]
Homing request
External signal
Forced stop cancelling
Upper limit signal status
Lower limit signal status
Stop status
State
4: Standstill
Signal state
ON
RUN
ON
Ready [X0]
ON
Module access enabled
FALSE
Not used
FALSE
Homing request FALSE
TRUE
Emergency stop input FALSE
(Forced stop cancel)
FALSE
Within the upper limit range
FALSE
Within the lower limit range
FALSE
Stop signal (STOP) FALSE
State
4: Standstill
4: GroupStandby
Signal state
ON
RUN
ON
Ready [X0]
ON
Module access enabled
FALSE
Homing request FALSE
TRUE
Emergency stop input
FALSE (Forced stop cancel)
FALSE
Within the upper limit range
FALSE
Within the lower limit range
FALSE
Stop signal (STOP) FALSE
Variable name
AxisName.Md.AxisStatus
Variable name
System.Cd.SequenceReady
System.Md.Ready
System.Md.Sync
AxisName.Md.UseInGroup
AxisName.Md.Homing_Request
AxisName.Md.ForcedStop_Released
AxisName.Md.HwStrokeLimit_FlsStatus
AxisName.Md.HwStrokeLimit_RlsStatus
AxisName.Md.StopStatus
Variable name
AxisName.Md.AxisStatus
AxesGroupName.Md.AxesGroupStatus
Variable name
System.Cd.SequenceReady
System.Md.Ready
System.Md.SyncFlag
AxisName.Md.Homing_Request
AxisName.Md.ForcedStop_Released
AxisName.Md.HwStrokeLimit_FlsStatus
AxisName.Md.HwStrokeLimit_RlsStatus
AxisName.Md.StopStatus
4 START AND STOP
4
105
4.1 Start